Power Cable Wire Gauge And Circuit Breaker Selection - Gree GMV-24WL/C-T Service Manual

Dc inverter side discharge vrf ⅱ for north america
Hide thumbs Also See for GMV-24WL/C-T:
Table of Contents

Advertisement

GREE
(2) The wiring diagram for power cord of outdoor unit and communication wire.
There are two wiring diagrams for communication wires of indoor/outdoor units and remote monitor:
1) Real line method;
2) Broken line method. Please select it based on the actual installation situation.
There are two wiring diagrams for power cord:
1) Real line method;
2) Broken line method. Please select it based on the actual installation situation.

7.2 Power Cable Wire Gauge and Circuit Breaker Selection

Model
Power supply
GMV-24WL/C-T(U)
GMV-28WL/C-T(U)
GMV-36WL/A-T(U)
GMV-48WL/A-T(U)
GMV-60WL/A-T(U)
GMV-36WL/C-T(U)
GMV-48WL/C-T(U)
GMV-60WL/C-T(U)
Max Fuse Size/Fusible
208/230V~
60Hz
208/230V~
60Hz
208/230V~
60Hz
208/230V~
60Hz
208/230V~
60Hz
208/230V~
60Hz
208/230V~
60Hz
208/230V~
60Hz
DC Inverter Side Discharge VRF Ⅱ for North America
Max Ckt, Bkr Size/Disjoncteur
Max.
(A)
25
30
35
45
60
35
40
40
85
Max. (A)
25
30
35
45
60
35
40
40
Min. Circuit
Ampacity
(A)
21
21
31
34
39.8
28.5
33
34.5