Condensate Water Pipe; Insulation Material; Communication Cable And Control Cable - Gree GMV-24WL/C-T Service Manual

Dc inverter side discharge vrf ⅱ for north america
Hide thumbs Also See for GMV-24WL/C-T:
Table of Contents

Advertisement

GREE
(3) Test report: Certifications and quality test reports must be provided.
(4) The tensile strength must be at least 240 kgf/mm² .
(5) Specifications requirement
OD (mm/inch)
Φ6.35(1/4)
Φ9.52(3/8)
Φ12.70(1/2)
Φ15.9(5/8)
Φ19.05(3/4)
(6) After the inner part of the copper pipe is cleaned and dried, the inlet and outlet must be sealed
tightly by using pipe caps, plugs or adhesive tapes. .

2.2 Condensate water pipe

(1) Pipes that can be used for air conditioner drainage include: water supplying UPVC pipe, PP-R
pipe, PP-C pipe, and HDG steel pipe;
(2) All relevant certificates and quality test reports are provided.
(3) Requirements for specifications and wall thickness
(4) Water supplying UPVC pipe: Φ32mm×2mm,Φ40mm×2mm,Φ50mm×2.5mm;
(5) HDG steel pipe: Φ25mm×3.25mm,Φ32mm×3.25mm,Φ40mm×3.5mm,Φ50mm×3.5mm.

2.3 Insulation material

(1) Rubber foam insulation material;
(2) Flame retardancy level: B1 or higher;
(3) Refractoriness: at least 120℃(248℉);
(4) The insulation thickness of condensate water pipe: at least 10 mm;
(5) When the diameter of copper pipe is equal to or greater than Φ15.9 mm, the thickness of
insulation material should be at least 20 mm; when the diameter of copper pipe is less than
15.9 mm, the thickness of insulation material should be at least 15 mm.

2.4 Communication cable and control cable

Note: For air conditioning units installed in places with strong electromagnetic interference, shielded
wire must be used as the communication cables of the IDU and wired controller, and shielded twisted
pairs must be used as the communication cables between IDUs and between the IDU and ODU.
Communication cable selection for ODU and IDUs
DC Inverter Side Discharge VRF Ⅱ for North America
R410A Refrigerant System
Wall Thickness (mm/inch)
≥0.8(1/32)
≥0.8(1/32)
≥0.8(1/32)
≥1.0(1/25)
≥1.0(1/25)
66
Model
0
0
0
0
0

Hide quick links: