3.7 Installation space requirement

If all sides of the ODU (including the top) are surrounded by walls, process according to the
following requirements for installation space:
4 Installation of Electronic Expansion Valve Assy (unit with
external EXV)
The EXV of indoor unit is built-in.

5 Installation of Refrigerant Pipeline

5.1Allowable Length and Height Difference of Connection Pipe

Y type branch joint is adopted to connect indoor and outdoor units. Connecting method is shown in
the figure below:
NOTICE! Equivalent length of one Y-type branch is 0.5m(1-5/8feet).
A
B
900
340
(35 7/16)
(13 3/8)
940
320
(37)
(12 9/16)
900
340
(35 3/8)
(13 3/8)
940
320
(37)
(12 9/16)
Fig.3
DC Inverter Side Discharge VRF Ⅱ for North America
C
1345
(53)
1430
(56 1/4)
1345
(53)
1430
(56 1/4)
70
Unit:mm(inch)
D
572
378
(22 1/2)
(15)
632
350
(24 7/8)
(14 7/8)
572
378
(22 1/2)
(15)
632
350
(24 7/8)
(14 7/8)
Fig.4