5.5 Dimension of Pipe between Indoor Branch and IDU

Dimension of pipe between indoor branch and IDU should be consistent with the dimension of
indoor pipe.
Rated capacity of IDU
9600<C≤17000
17000<C≤48000
48000<C≤55000
55000<C≤96000
NOTICE! If the distance between IDU and its nearest branch is over 10m(33feet), then the liquid
pipe of IDU (rated capacity ≤17000Btu/h) shall be enlarged.
C (Btu/h)
C ≤19000
19000<C≤48500
48500<C≤76400
C(Btu/h)
C≤9600
DC Inverter Side Discharge VRF Ⅱ for North America
Pipe
(mm/inch)
Φ12.7
(Φ1/2)
Φ15.9
(Φ5/8)
Φ19.05
(Φ3/4)
Fig. 9
Gas pipe
(mm/inch)
Φ9.52
(Φ3/8)
Φ12.7
(Φ1/2)
Φ15.9
(Φ5/8)
Φ19.05
(Φ3/4)
Φ22.2
(Φ7/8)
74
Liquid pipe
(mm/inch)
Φ6.35
(Φ1/4)
Φ9.52
(Φ3/8)
Φ9.52
(Φ3/8)
Liquid pipe
(mm/inch)
Φ6.35
(Φ1/4)
Φ6.35
(Φ1/4)
Φ9.52
(Φ3/8)
Φ9.52
(Φ3/8)
Φ9.52
(Φ3/8)