Selection Of Indoor Branches; Dimension Of Pipe Between Indoor Branches - Gree GMV-24WL/C-T Service Manual

Dc inverter side discharge vrf ⅱ for north america
Hide thumbs Also See for GMV-24WL/C-T:
Table of Contents

Advertisement

GREE

5.3 Selection of Indoor Branches

Select indoor branches according to the total capacity of downstream indoor units. if the capacity
exceeds that of the outdoor unit, capacity of outdoor unit prevails.
Refrigerant system
Y type branch

5.4 Dimension of Pipe between Indoor Branches

Select pipe between indoor branches according to the capacity of downstream indoor units; if the
capacity exceeds that of the outdoor unit, capacity of outdoor unit prevails.
DC Inverter Side Discharge VRF Ⅱ for North America
Fig.7
Total capacity of downstream indoor units C (Btu/h)
C< 68200
68200≤C≤102400
102400<C ≤238800
238800<C ≤460600
460600<C
Fig.8
73
Model
FQ01A/A
FQ01B/A
FQ02/A
FQ03/A
FQ04/A