DL-10 – RS-485 Remote Temperature and Humidity

Holding Register (4xxxx)

Register
Points
DEC
HEX
40449
1C0
1
40485
1E4
1
40486
1E5
1
Copyright © 2019 ICP DAS CO., Ltd. All Rights Reserved.
Description
Read/Write the temperature offset
value (unit: 0.01℃)
Read/Write the Device ID
Read/Write the Baud Rate (bps)
and Data Format
Bit-5:Bit-0 (Baud Rate)
03: 1200
04: 2400
05:4800
06: 9600
07: 19200
08: 38400
09: 57600
0A:115200
Bit-7:Bit-6 (Data Format)
00: no parity, 1 Stop bit
01: no parity, 2 Stop bits
10: even parity, 1 Stop bit
11: odd parity, 1 stop bit
Data Format
Attribute
-32767 ~
R/W
32768
1 ~ 247
R/W
0x03 ~ 0xCA
R/W
Factory
Value
0