LEGRAND ELIOT Kit STOP&GO Connected Manual page 7

Table of Contents

Advertisement

ELIOT Kit STOP&GO Connected
4. PREPARATION - CONNECTION
On site information displayed by the Stop&Go
Details for "too recurrent" non-permanent faults:
During its functioning, the Stop&Go memorises the numbers of
faults and of remote/manual resetting operations.
. When an event occurs, the Stop&Go analyses the event and in
case of fault (short-circuit or ground fault) it starts the recurring fault
procedure.
. See table for details:
Period
# of faults
≤ 5 minutes
3
≤ 1 hour
3
≤ 1 day
5
≤ 7 days
7
≤ 30 days
15
Selector AUTO / MAN:
. Enables and disables the remote command of the Stop&Go.
. Possible states:
- AUTO: allows to remotely control the
Stop&Go via the Smartphone app (reclosing of
the associated device following a fault).
- MAN: on-site manual control only by the
handle of the Stop&Go (isolating and power
handles together)
Note: in case of on-site maintenance, to put the selector on MAN is
not enough. The use of a padlock is the only secured way
Technical data sheet: F02465EN/01
(continued)
(continued)
Consequence
- Remote resetting is disabled.
- The application shows this state
with the following message:
- The application shows this
condition with a message indicating
the number of faults within the time
frame and the indication to check the
electrical installation on site.
- Remote resetting remains enabled.
Updated: 28/03/2019
Cat. N°: 4 149 54
4. PREPARATION - CONNECTION
:
Stop&Go signalling led:
Possible states:
Led colour
Fast blinking
red
Steady
Fast blinking
green
Steady
Switched-off
Wi-Fi module signalling led:
. Power led: indicates the status of operation of the interface:
-
Steady green → interface supplied
-
Steady off → interface not supplied
(continued)
State
Meaning
Waiting for manual or remote
reset command following a
temporary fault (non-permanent)
If the Stop&Go detects a too
recurrent fault, remote actuation is
disabled
"Unwanted tripping": Stop&Go has
detected a permanent default in
the system
Remote actuation is disabled
Stop&Go in MAN mode
"Normal situation": associated
device is powered and Stop&Go in
AUTO mode.
Stop&Go not supplied or sliding
front face downward
Created: 06/10/2016