1MRS758335 B
3.2.2
3.2.3
REU611
Application Manual
GUID-2D549B56-6CF7-4DCB-ACDE-E9EF601868A8 V1 EN
Figure 9:
Input switch group ISWGAPC

Output switch group OSWGAPC

The output switch group OSWGAPC has a number of inputs and one output. Every
input and output has a read-only description. OSWGAPC is used for connecting one
or several inputs to the output of the switch group via OR logic. Each input can be set
to be connected or not connected with the OR logic via the "IN_x connection"
settings. The output of OR logic is routed to switch group output.
GUID-1EFA82D5-F9E7-4322-87C2-CDADD29823BD V1 EN
Figure 10:
Output switch group OSWGAPC

Selector switch group SELGAPC

The selector switch group SELGAPC has a number of inputs and outputs. Every input
and output has a read-only description. Each output can be set to be connected with
one of the inputs via the OUT_x connection setting. An output can also be set to be not
connected with any of the inputs. In SELGAPC, one output signal can only be
connected to one input signal but the same input signal can be routed to several output
signals.