Section 3
REU611 standardized configuration
40
Channel number
Binary channel 13
Binary channel 14
Binary channel 15
Binary channel 16
Binary channel 17
Binary channel 18
Binary channel 19
Binary channel 20
Binary channel 21
Binary channel 22
Binary channel 23
Binary channel 24
Binary channel 25
Binary channel 26
Binary channel 27
Binary channel 28
Binary channel 29
Binary channel 30
Binary channel 31
SELGAPC1
IN_3
OUT_3
X120-BI3
CB Open Position
OR
TRPPTRC1_TRIP
TRPPTRC2_TRIP
GUID-EC303A9E-DD21-4501-A0C9-82EBC49AA114 V1 EN
Figure 21:
Trip circuit supervision
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by
the master trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open position.
The TCS alarm indication is connected to LED 7.
Channel ID text
ROVPTOV3_START
FRPFRQ1_START
FRPFRQ2_START
PHPTOV_OPERATE
PHPTUV_OPERATE
ROVPTOV_OPERATE
PSPTUV/NSPTOV_OPERATE
FRPFRQ_OPERATE
SELGAPC1_Blocking 1
SELGAPC1_CB_Closed
SELGAPC1_CB_Open
SELGAPC1_External Trip
SG_1_ACT
SG_2_ACT
SG_3_ACT
SG_4_ACT
SG_5_ACT
SG_6_ACT
BUS_VT_MCB_OPEN
TRIP CIRCUIT SUPERVISION
SELGAPC2
TCSSCBR1
OUT_1
BLOCK
IN_2
OUT_2
TCSSCBR2
BLOCK
1MRS758335 B
Level trigger mode
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
1=positive or rising
OSWGAPC12
SELGAPC4
IN_2
ALARM
IN_13
OUT
OR
IN_3
ALARM
Application Manual
OUT_7
LED 7
REU611

Advertisement