ABB Relion Applications Manual page 48

Voltage protection and control
Hide thumbs Also See for Relion:
Table of Contents

Advertisement

Section 3
REU611 standardized configuration
42
TRPPTRC1 and TRPPTRC2 provide the lockout/latching function, event generation
and the trip signal duration setting. One binary input through SELGAPC1 can be
connected to the RST_LKOUT input of the master trip. If the lockout operation mode
is selected, it is used to enable external reset.
SELGAPC1
X120-BI2
IN_2
OUT_2
CB Closed Position
IN_3
OUT_3
X120-BI3
CB Open Position
IN_5
OUT_5
Always True
TRPPTRC1_TRIP
TRPPTRC2_TRIP
GUID-798F8D1E-A9AA-47A1-8A27-EAB36E989637 V2 EN
Figure 23:
Circuit breaker control
The ENA_CLOSE input, which enables the closing of the circuit breaker, is
interlocked by two master trip signals. Any trip blocks the breaker from closing. An
always true signal is also connected to ENA_CLOSE via SELGAPC1 by default. The
open operation is always enabled.
CIRCUIT BREAKER CONTROL
CBXCBR1
SELECTED
POSOPEN
EXE_OP
POSCLOSE
EXE_CL
ENA_OPEN
OP_REQ
ENA_CLOSE
CL_REQ
BLK_OPEN
OPENPOS
BLK_CLOSE
CLOSEPOS
AND
AU_OPEN
OKPOS
AU_CLOSE
TRIP
OPEN_ENAD
SYNC_OK
CLOSE_ENAD
SYNC_ITL_BYP
1MRS758335 B
CBXCBR1_EXE_OP
SELGAPC3
IN_3
OUT_1
X100 PO1
REU611
Application Manual