Supervision - ABB ACS880 PCP Firmware Manual

Control program
Table of Contents

Advertisement

No.
Name/Value
32

32 Supervision

32.01
Supervision status
Bit
Name
0
Supervision 1 active
1
Supervision 2 active
2
Supervision 3 active
3...15
Reserved
0000...0111b
32.05
Supervision 1
function
Disabled
Low
High
Abs low
Abs high
Both
Abs both
32.06
Supervision 1 action
No action
Warning
Fault
32.07
Supervision 1 signal
Zero
Description
Configuration of signal supervision functions 1...3.
Three values can be chosen to be monitored; a warning or
fault is generated whenever predefined limits are
exceeded.
See also section
Signal supervision
Signal supervision status word.
Indicates whether the values monitored by the signal
supervision functions are within or outside their respective
limits.
Note: This word is independent of the drive actions
defined by parameters 32.06,
Description
1 = Signal selected by
1 = Signal selected by
1 = Signal selected by
Signal supervision status word.
Selects the mode of signal supervision function 1.
Determines how the monitored signal (see parameter
32.07) is compared to its lower and upper limits
32.10
respectively). The action to be taken when the
condition is fulfilled is selected by 32.06.
Signal supervision 1 not in use.
Action is taken whenever the signal falls below its lower
limit.
Action is taken whenever the signal rises above its upper
limit.
Action is taken whenever the absolute value of the signal
falls below its (absolute) lower limit.
Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
Action is taken whenever the signal falls below its low limit
or rises above its high limit.
Action is taken whenever the absolute value of the signal
falls below its (absolute) low limit or rises above its
(absolute) high limit.
Selects the action the drive takes when the value
monitored by signal supervision 1 exceeds its limits.
Note: This parameter does not affect the status indicated
by
32.01 Supervision
status.
No action taken.
A warning
(A8B0 Signal
The drive trips on
80B0 Signal
Selects the signal to be monitored by signal supervision
function 1.
None.
(page 89).
32.16
and 32.26.
32.07
is outside its limits.
32.17
is outside its limits.
32.27
is outside its limits.
(32.09
supervision) is generated.
supervision.
Parameters 251
Def/
FbEq16
0000b
1 = 1
Disabled
and
0
1
2
3
4
5
6
No action
0
1
2
Zero