Multi-function MO Output by AI Level Source

Settings
AI Upper Level 1
Settings

AI Lower Level 2

Settings
 Multi-function output terminal 67 must work with Pr.03-44 to select input channels. When analog
input level is higher than Pr.03-45, multi-function output acts; when analog input level is lower
than Pr.03-46, multi-function output terminals stop outputting.
 When setting levels, AI upper level must be higher than AI lower level.

Analog Input Curve Selection

Settings
ACI Lowest Point
Settings
ACI Proportional Lowest Point
Settings
ACI Mid-point
Settings
ACI Proportional Mid-point
Settings
ACI Highest Point
Settings
ACI Proportional Highest Point
Settings
0: AVI
1: ACI
-100–100%
-100–100%
0: Regular Curve
1: Three-point curve of AVI (& AI10)
2: Three-point curve of ACI (& AI11)
Pr.03-28 ≠ 1, 0.00–20.00 mA
Pr.03-28 ≠ 1, 0.00–100.00%
Pr.03-28 ≠ 1, 0.00–20.00 mA
Pr.03-28 ≠ 1, 0.00–100.00%
Pr.03-28 ≠ 1, 0.00–20.00 mA
Pr.03-28 ≠ 1, 0.00–100.00%
12.1-03-17
Chapter 12 Description of Parameter SettingsME300
Default: 0
Default: 50
Default: 10
Default: 0
Default: 4.00
Default: 0.00
Default: 12.00
Default: 50.00
Default: 20.00
Default: 100.00