02 Digital Input / Output Parameters

Two-wire / Three-wire Operation Control

Settings
 In the Quick Start function, the output remains ready for operation. The drive responds to the
Start command immediately.
 When using Quick Start function, the output terminals UVW are with driving voltages in order to
output and respond immediately if a Start command is given. Do not touch the terminals or modify
the motor wiring to prevent electric shocks.
 This parameter sets the configuration of the external drive operation control and the Quick Start
function. There are six different control modes listed in the following table.
Pr.02-00
Setting value: 1
Two-wire
FWD / STOP
REV / STOP
Setting value: 2
Two-wire
RUN / STOP
FWD / REV
Setting value: 3
Three-wire
0: No function
1: Two-wire mode 1, power on for operation control
(M1: FWD / STOP, M2: REV / STOP)
2: Two-wire mode 2, power on for operation control
(M1: RUN / STOP, M2: FWD / REV)
3: Three-wire, power on for operation control
(M1: RUN, M2: REV / FWD, M3: STOP)
4: Two-wire mode 1, Quick Start
(M1: FWD / STOP, M2: REV / STOP)
5: Two-wire mode 2, Quick Start
(M1: RUN / STOP, M2: FWD / REV)
6: Three-wire, Quick Start
(M1: RUN, M2: REV / FWD, M3: STOP)
12.1-02-1
Chapter 12 Description of Parameter SettingsME300
 You can set this parameter during operation.
External Terminal Control Circuits
Default: 1