Chapter 15 Safe Torque Off FunctionME300
15-7-2 Troubleshooting Instructions
Refer to the following instructions for troubleshooting when STO / STL1 / STL2 / STL3 appears on
the keypad. Refer to Chapter 14 Error Codes.
Digital keypad
ID No.
72
76
77
78
Display
S1–DCM internal loop detection error
Corrective Actions
Check the wiring of the S1 terminal.
Reset the emergency switch (ON: activated) and cycle the
power.
Check that the input voltage maintains at least 11 V.
Check the wiring of the S1 and +24 V terminals.
After you make sure all the wiring is correct, if STL1 fault still
exists after cycling the power, please contact Delta.
Safe Torque Off function active
Corrective Actions
Check the wiring of the S1 and S2 terminals.
Reset the emergency switch (ON: activated) and cycle the
power.
Check that the input voltage maintains at least 11 V.
Check the wiring of the S1 / S2 and +24 V terminals.
After you make sure all the wiring is correct, if STO fault still
exists after cycling the power, please contact Delta.
S2–DCM internal loop detection error
Corrective Actions
Check the wiring of the S2 terminal.
Reset the emergency switch (ON: activated) and cycle the
power.
Check that the input voltage maintains at least 11 V.
Check the wiring of the S2 and +24 V terminals.
After you make sure all the wiring is correct, if STL2 fault still
exists after cycling the power, please contact Delta.
S1–DCM & S2–DCM internal loop detection error
Corrective Actions
After you make sure all the wiring is correct, if STL3 fault still
exists after cycling the power, please contact Delta.
Table 5: Digital keypad troubleshooting instructions