Technical Parameters - Goodwe MS Series User Manual

Solar inverter
Hide thumbs Also See for MS Series:
Table of Contents

Advertisement

Type of fault
Relay-Check Failure
DCI Injection High
Inverter
1. Disconnect the DC connector and AC.
EEPROM R/W Failure
2. Reconnect the DC connector.
failure
SPI Failure
3. If the problem still exists, please call the local service office.
DC BUS High
GFCI Failure
1. Turn off DC switch, take off DC connector, measure the voltage of PV array.
2. Plug in DC connector, and turn on DC switch.
Others
No display
3. If PV array voltage is lower than 150V , please check configuration of invert
module.
4. If voltage is higher than 150V and the problem still exists, please contact
local office.
Note:
When sunlight is insufficient, the PV Inverter may continuously start up and shut down automati-
cally due to insufficient power generated by the PV panel.
21
Troubleshooting

7 Technical Parameters

Technical Data
GW5000-MS
PV Input Data
Max. DC Input Power (Wp)
10000
Max. DC Input Voltage (V)
600
MPPT Range (V)
80~550
Start-up Voltage (V)
80
Min. Feed-in Voltage(V)
120
Nominal DC Input Voltage (V)
360
Max. Input Current (A)
12.5/12.5/12.5
Max. Short Current (A)
15/15/15
No. of MPP Trackers
3
No. of Input Strings per Tracker
1/1/1
AC Output Data
Nominal Output Power (W)
5000
Max. Output Apparent Power (VA)
5500
Nominal Output Voltage (V)
220/230
Nominal Output Frequency (Hz)
50/60
Max. Output Current (A)
25
Output Power Factor
Output THDi (@Nominal Output)
Efficiency
Max. Efficiency
97.7%
European Efficiency
97.3%
Protection
Anti-islanding Protection
Input Reverse Polarity Protection
Insulation Resistor Detection
Residual Current Monitoring Unit
Output Over Current Protection
Output Short Protection
Output Over Voltage Protection
DC SPD Protection
AC SPD Protection
General Data
Operating Temperature Range (℃)
Relative Humidity
Operating Altitude(m)
Cooling
User Interface
Communication
Weight (kg)
Size (Width*Height*Depth mm)
Protection Degree
Night Self Consumption (W)
Topology
Certifications & Standards
Grid Regulation
Safety Regulation
EMC
GW6000-MS
GW7000-MS
GW8500-MS
12000
13500
13500
600
600
600
80~550
80~550
80~550
80
80
80
120
120
120
360
360
360
12.5/12.5/12.5
12.5/12.5/12.5
12.5/12.5/12.5
15/15/15
15/15/15
15/15/15
3
3
3
1/1/1
1/1/1
1/1/1
6000
7000
8500
6600
7700
9350
220/230
220/230
220/230
50/60
50/60
50/60
30
35
42.5
~1 (Adjustable from 0.8 leading to 0.8 lagging)
<3%
97.7%
97.7%
97.7%
97.3%
97.3%
97.3%
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Type II
Type III (Type II optional)
-25~60
0~100%
≤4000
Natural Convection
LCD & LED
RS485; WiFi/LAN(optional)
22.5
415*511*175
IP65
<1
Transformerless
Visit homepage to achieve information.
GW10K-MS
13500
600
80~550
80
120
360
12.5/12.5/12.5
15/15/15
3
1/1/1
10000
10000
220/230
50/60
45.5
97.7%
97.3%
22

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gw5000-msGw6000-msGw7000-msGw8500-msGw10k-ms

Table of Contents