Operating the NI PS-17
Serial Operation
Caution
Avoid return voltage (for example, from a decelerating motor or battery) which is
applied to the output terminals.
© National Instruments
This section provides general information on the operation of the NI PS-17
power supply.
The NI PS-17 can operate in series to increase the output voltage.
Figure 2-3 shows the NI PS-17 in a serial configuration.
Figure 2-3. NI PS-17 in Serial Operation
Before operating the NI PS-17 in a serial configuration, consider the
following:
•
It is possible to connect as many units in series as needed, providing
the sum of the output voltage does not exceed 150 V
•
Voltages with a potential above 60 V
more and can be dangerous. Such voltages must be installed with a
protection against touching.
•
Use power supplies of the same type for serial operation.
•
Earthing of the output is required when the sum of the output voltage
is above 60 V
.
DC
•
Keep an installation clearance of 15 mm (left/right) between two
power supplies and avoid installing the power supplies on top of each
other.
Chapter 2
Unit A
AC
+
–
DC
Unit B
AC
+
–
DC
DC
2-5
Installation and Configuration
+
Load
–
Earth
.
DC
are not SELV-compliant any
NI PS-17 Power Supply User Manual