Warranty The NI PS-16 is warranted against defects in materials and workmanship for a period of one year from the date of shipment, as evidenced by receipts or other documentation. National Instruments will, at its option, repair or replace equipment that proves to be defective during the warranty period.
Page 4
EVALUATED OR CONTEMPLATED BY NATIONAL INSTRUMENTS, THE USER OR APPLICATION DESIGNER IS ULTIMATELY RESPONSIBLE FOR VERIFYING AND VALIDATING THE SUITABILITY OF NATIONAL INSTRUMENTS PRODUCTS WHENEVER NATIONAL INSTRUMENTS PRODUCTS ARE INCORPORATED IN A SYSTEM OR APPLICATION, INCLUDING, WITHOUT LIMITATION, THE APPROPRIATE DESIGN, PROCESS AND SAFETY LEVEL OF SUCH SYSTEM OR APPLICATION.
Operation of this hardware in a residential area is likely to cause harmful interference. Users are required to correct the interference at their own expense or cease operation of the hardware. Changes or modifications not expressly approved by National Instruments could void the user’s right to operate the hardware under the local regulatory rules.
Page 7
Peak Current Capability .................. A-8 Efficiency and Power Losses..................A-8 Reliability ........................A-9 Dielectric Strength......................A-10 Used Substances ......................A-11 Environment ........................A-12 Protection Features ......................A-13 Appendix B Technical Support and Professional Services Index NI PS-16 Power Supply User Manual viii ni.com...
About This Manual The NI PS-16 Power Supply User Manual describes the features and specifications of the NI PS-16 power supply and contains information about installing the power supply. Conventions The following conventions are used in this manual: » The » symbol leads you through nested menu items and dialog box options to a final action.
The following documents contain information that you might find helpful as you read this manual: • NI PS-15/16/17 Side Mount Brackets Installation Guide • NI PS-15/16/17 Panel Mount Brackets Installation Guide • NI PS-15/16/17 Instruction Manual NI PS-16 Power Supply User Manual ni.com...
Printed NI PS-15/16/17 Instruction Manual Key Features The NI PS-16 includes a power reserve of 20%. This extra current may be used continuously at temperatures up to +45 °C. Additionally, the AC 100–120 V/200–240 V Auto-select input makes worldwide installation and usage very simple.
Appendix A, Specifications. Power Supply Description Figures 1-1 and 1-2 show the functional description and front panel features of the NI PS-16 power supply. Figure 1-1 provides the functional diagram for the NI PS-16. Output Voltage Regulator...
Chapter 1 Getting Started Figure 1-2 provides the front panel features of the NI PS-16. DC 24 V 10 A DC OK NI PS-16 Power Supply AC 100-120 / 200-240 V 1 Output Terminals 3 DC OK LED 2 Output Voltage Potentiometer 4 Input Terminals Figure 1-2.
The output voltage may be adjusted above 28 V by the potentiometer, but voltages beyond 28 V are not guaranteed. Output voltages greater than 28 V are not supported on an NI PS-16 unit. Note DC OK LED This green LED indicates the status of available DC power through the output terminals.
PANEL MOUNTING KIT FOR NI PS-15/16/17 Side Mounting Kit The Side Mounting Kit (199430-01) allows you to mount the NI PS-16 on its side to a wall, panel surface, or a DIN-Rail for reduced installation depth. Refer to the NI PS-15/16/17 Side Mount Brackets Installation Guide for more information.
Installation and Configuration This chapter describes how to prepare and operate the NI PS-16 power supply. Mounting Orientation and Installation This section describes the different mounting orientations, and the effect that mounting orientation has on power supply performance. Mounting orientations other than input terminals on the bottom and output on the top require a reduction in continuous output power or a limitation in the maximum allowed ambient temperature.
Page 16
Ambient Temperature 60°C Output Current 12 A Mounting Orientation D (Horizontal ccw) Ambient Temperature 60°C Output Current 12 A Mounting Orientation E (Horizontal ccw) Ambient Temperature 60°C Figure 2-1. NI PS-16 Mounting Orientations NI PS-16 Power Supply User Manual ni.com...
Mounting Equipment section of Chapter 1, Getting Started. Wiring The Terminals This section describes wiring for the NI PS-16 power supply. Table 2-1 provides a list of basic requirements for wiring. Table 2-1. Wiring Requirements Type Spring-Clamp Terminals Solid wire 0.5–6 mm...
Page 18
Ensure that all wires are properly seated and not loose. Ensure that the rest of your equipment is ready to be powered without creating a hazard. Apply MAINS voltage to the NI PS-16 power supply. NI PS-16 Power Supply User Manual ni.com...
Chapter 2 Installation and Configuration Operating the NI PS-16 This section provides general information on the operation of the NI PS-16 power supply. Serial Operation The NI PS-16 can operate in series to increase the output voltage. Figure 2-3 shows the NI PS-16 in a serial configuration.
The simplest way is to put two NI PS-16 power supplies in parallel. If one power supply unit fails, the other one is automatically able to support the load current without any interruption.
Protection section. External Input Protection The NI PS-16 power supply is tested and approved for branch circuits up to 20 A. External protection is only required if the supplying branch has an ampacity greater than 20 A. In some countries local regulations might apply, so check local codes and local requirements.
However, you must not cover the ventilation grid (for example, with cable conduits) by more than 30%. Proper installation clearance for the NI PS-16 is 40 mm on top, 20 mm on the bottom, 5 mm on the left and right side when loaded permanently with full power.
Loads such as decelerating motors and inductors can feed voltage back to the power supply. This feature is also called return voltage immunity or resistance against back-EMF (Electromagnetic Force). The NI PS-16 power supply is resistant to this and does not malfunction when a load feeds back voltage to the power supply, regardless of whether the power supply itself is on or off.
Specifications This appendix contains specifications for the NI PS-16 power supply. Specifications are subject to change without notice. Note Must be mounted in an enclosure by qualified personnel. Refer to Hazardous Voltages Figure A-1 for more information. This power supply is designed for installation in an enclosure and is intended for general use, such as in industrial control, office, communication, and instrumentation equipment.
Page 27
Appendix A Specifications 1 Suitably rated NEMA or IP enclosure that requires tool access 2 NI PS-16 Power Supply Figure A-1. NI PS-16 Power Supply 38.1 + + – – DC 24 V 10 A 24–28 V DC OK AC 100-120 / 200-240 V Depth: 117 mm (4.61 in.)
Page 29
Figure A-3. Input Voltage Range Intput Voltage –5% Output Voltage Rise Start-up Time Delay Figure A-4. Turn On Behavior, Definitions Input Current, Typ. Output Current 10 11 12 A Figure A-5. Input Current vs. Output Load NI PS-16 Power Supply User Manual ni.com...
– 5% Output Voltage Hold-up Time Figure A-9. Shutdown Behavior, Definitions Note At no load, the hold-up time can be up to several seconds. The green DC OK LED is lit during this time. NI PS-16 Power Supply User Manual ni.com...
Typical 12.0 W 12.3 W 11.3 W 5 A, 24 V Typical 24.6 W 23.7 W 23.2 W 10 A, 24 V Typical 31.9 W 29.6 W 27.9 W 12 A, 24 V NI PS-16 Power Supply User Manual ni.com...
Reliability The lifetime expectancy shown in Table A-1 indicates the service life of the NI PS-16, and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours. Lifetime expectancy is calculated according to the capacitor’s manufacturer specification.
+ pole, the – pole or any other part of the output circuit should be connected to the protective earth system. This helps to avoid situations in which a load starts unexpectedly or can not be switched off when unnoticed earth faults occur. NI PS-16 Power Supply User Manual A-10 ni.com...
Input Output – Earth, PE Figure A-12. Dielectric Strength Table A-2 lists the tests that have been run to determine the NI PS-16 dielectric strength, and the results of each test. Table A-2. Dielectric Strength Test Results Test Duration Type test...
Above 2000 m (6500 ft), refer to Figure A-14 Over-voltage category EN 50178, altitudes up to 2000 m Altitudes from 2000 m to 6000 m Degree of pollution EN 50178, not conductive NI PS-16 Power Supply User Manual A-12 ni.com...
2000 4000 6000 m Figure A-14. Output Current vs. Altitude Note The ambient temperature is defined as the temperature 2 cm below the NI PS-16. Protection Features Output protection Electronically protected against overload, no-load and short-circuits Output over-voltage Typical 35 V...
4 kV Criterion A → Surge voltage on output EN 61000-4-5 – 500 V Criterion A → +/– 500 V Criterion A Conducted disturbance EN 61000-4-6 0.15–80 MHz 10 V Criterion A NI PS-16 Power Supply User Manual A-14 ni.com...
Page 41
For EMC compliance, operate this device with shielded cabling. CE Compliance This product meets the essential requirements of applicable European Directives as follows: • 2006/95/EC; Low-Voltage Directive (safety) • 2004/108/EC; Electromagnetic Compatibility Directive (EMC) NI PS-16 Power Supply User Manual A-16 ni.com...
Certification column. Environmental Management National Instruments is committed to designing and manufacturing products in an environmentally responsible manner. NI recognizes that eliminating certain hazardous substances from our products is beneficial to the environment and to NI customers.
Technical Support and Professional Services Visit the following sections of the award-winning National Instruments Web site at for technical support and professional services: ni.com • Support—Technical support at includes the ni.com/support following resources: – Self-Help Technical Resources—For answers and solutions,...
Page 44
You also can visit the Worldwide Offices section of ni.com/niglobal to access the branch office Web sites, which provide up-to-date contact information, support phone numbers, email addresses, and current events. NI PS-16 Power Supply User Manual ni.com...
Page 46
AC input, A-3 CE compliance, A-16 certifications, A-17 operating in a sealed enclosure, 2-7 current inrush surge, A-5 operation dielectric strength, A-10 parallel, 2-6 dimensions, A-1 serial, 2-5 efficiency, A-8 figure, 2-5 electromagnetic compatibility, A-14 NI PS-16 Power Supply User Manual ni.com...
Page 47
2-6 hold-up time, A-6 figure, 2-6 online product certification, A-17 output, A-7 peak current capability, A-8 unpacking the NI PS-16 power supply, 1-1 power loss, A-8 use for charging batteries, 2-9 protection features, A-13 used substances specifications, A-11 reliability, A-9...