Table 5-12 Baud Rate / Character Frame (3964(R) Procedure) - Siemens SIMATIC S7-400 CP 440 Installation And Parameter Assignment

Point-to-point connection
Table of Contents

Advertisement

Configuring and Parameter Assignment the CP 440
5.4 Configuration data
Baud Rate / Character Frame
The following table describes the transmission rate/character frame.
Table 5-12
Baud Rate / Character Frame (3964(R) Procedure)
Parameters
Description
Baud rate
Speed of data transmission in bits per second (baud)
Start bit
During transmission, a start bit is prefixed to each character to
be sent.
Data bits
Number of bits onto which a character is mapped.
Stop bits
During transmission, stop bits are appended to every character
to be sent, indicating the end of the character.
Parity
A sequence of information bits can be extended to include
another bit, the parity bit. The addition of its value ("0" or "1")
brings the value of all the bits up to a defined status thus
enhancing parity.
A parity of "none" means that no parity bit is sent.
It is not possible to specify "none" if 7 data bits are set.
Priority
A partner has high priority if its send request takes precedence
over the send request of the other partner. A partner has low
priority if its send request must wait until the send request of the
other partner has been dealt with. With the 3964(R) procedure,
you must configure both communication partners with different
priorities, i.e. one partner is assigned high priority, the other low.
78
www.gkbpx.com
Point-to-point connection CP 440 Installation and Parameter Assignment
Value Range
Default Value
300
9600
600
1200
2400
4800
9600
19200
38400
57600
76800
115200
1 (fixed value)
7
8
8
1
1
2
none
even
odd
even
low
high
high