Input specifications:
current input:
Programmable ranges ................................. ± 10 and ± 20 mA
Functional range .......................................... -23 ... +23 mA
Input voltage drop ....................................... < 1 VDC @ 23 mA
voltage input:
Programmable ranges ................................. ± 5 and ± 10 V
Functional range .......................................... -11.5 ... +11.5 V
Input resistance ........................................... ≥ 1 MW
output specifications:
current output:
Programmable ranges ................................. 0...20 and 4...20 mA
Functional range .......................................... 0...23 mA
Load (max.) .................................................. 23 mA / 600 Ω
Load stability ............................................... ≤ 0.002% of span / 100 Ω
Current limit ................................................. ≤ 28 mA
voltage output:
Programmable ranges ................................. 0...5, 1...5, 0...10, 2...10 V
Functional range .......................................... 0...11.5 V
Load ........................................................... > 10 kW
of span = of the selected range
Input
type
All
EMC immunity influence ............................... < ±0.5% of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst ................. < ±1% of span
Accuracy values
Absolute
accuracy
≤ ± 0.05% of span
3 1 1 7 V 1 0 0 -UK
Temperature
coefficient
≤ ± 0.01% of span /°C