Turn off when UPS overload on battery
When this option is enabled, the programmable outlet will turn off when UPS is overload on battery
mode.
• Enable
• Disable (default)
Settings based on discharge time
Threshold of turing off the outlet (min)
• Enable
• Disable (default)
Sets the discharging time threshold of turning off of programmable outlet.
• 0 - 30 minutes (default of 5)
Threshold of when power returns for (min)
• Enable
• Disable (default)
Sets the turnning on waiting time of programmable outlet when power returns.
• 0 - 30 minutes (default of 0)
Settings based on backup time
Threshold of turing off the outlet (min)
• Enable
• Disable (default)
Sets the discharging time threshold of turning off of programmable outlet.
• 0 - 30 minutes (default of 5)
Threshold of when power returns for (min)
• Enable
• Disable (default)
Sets the turnning on waiting time of programmable outlet when power returns.
• 0 - 30 minutes (default of 0)
Settings based on capacity
Threshold of turing off the outlet (min)
• Enable
• Disable (default)
Sets the capacity threshold of turning off of programmable outlet.
• 20 - 80 % (default of 20)
26
Operations