Vertiv Liebert EXM TXC User Manual
Vertiv Liebert EXM TXC User Manual

Vertiv Liebert EXM TXC User Manual

10-100kva, 60hz
Table of Contents

Advertisement

Quick Links

Liebert® EXM™ TXC™
User Manual—10-100kVA, 60Hz

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Liebert EXM TXC and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Vertiv Liebert EXM TXC

  • Page 1 Liebert® EXM™ TXC™ User Manual—10-100kVA, 60Hz...
  • Page 2 The products covered by this instruction manual are manufactured and/or sold by Vertiv This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use or disclosure of it without the written permission of Vertiv is strictly prohibited.
  • Page 3: Table Of Contents

    ............6 Figure 2 Schematic - Liebert EXM TXC to Maintenance Bypass Cabinet ..... 8 Figure 3 Bolting Liebert EXM UPS to a Liebert EXM TXC .
  • Page 4 Table 4 Liebert EXM TXC, 10-100k, mechanical characteristics ......18 Table 5 Liebert EXM TXC heat dissipation, both transformers, full load.
  • Page 5: Important Safety Instructions

    Otherwise, human safety may be endangered and damage to the UPS will not be covered by the warranty. The Liebert EXM TXC is designed for commercial and industrial uses and cannot be used as life support equipment.
  • Page 6 Note also that the earth leakage currents of the load will be carried by this RCCB or RCD. This equipment must be earthed in accordance with the local electrical code of practice. ® ™ ™ Vertiv | Liebert User Manual |...
  • Page 7 (earth ground). Never work alone, even if all power is removed from the equipment. A second person should be standing by to assist and summon help in case an accident should occur. ® ™ ™ Vertiv | Liebert User Manual |...
  • Page 8 Ground connection is essential before connecting the input supply. This equipment must be grounded in accordance with local electrical codes. Maximum load must not exceed that shown on the UPS rating label. ® ™ ™ Vertiv | Liebert User Manual |...
  • Page 9 This unit is not designed for use in a residential area. Operation of this unit in a residential area may cause harmful interference that the user is solely responsible for correcting. ® ™ ™ Vertiv | Liebert User Manual |...
  • Page 10: Glossary Of Symbols

    AC input AC output Requests the user to consult the manual Indicates the unit contains a valve-regulated lead acid battery PbH2SO4 Recycle DC voltage AC voltage Equipment grounding conductor Bonded to ground ® ™ ™ Vertiv | Liebert User Manual |...
  • Page 11: Liebert Exm Txc

    OCATING THE ABINET This Liebert EXM TXC may be mounted to the right of the UPS. Ensure that the unit is in a well- ventilated area and that there is clearance for access to the switches and cable connections as required by national and local codes.
  • Page 12: Cable Installation

    NOTE If the Liebert EXM TXC is not to be bolted to the UPS, use either top or bottom access plate. 6. Connect the source #1 cables to TB1 (A-B-C) and tighten the connections to 192 lb-in (22Nm) for M10 bolt.
  • Page 13: Figure 2 Schematic - Liebert Exm Txc To Maintenance Bypass Cabinet

    NOTES All interconnection hardware supplied by Vertiv. 2. AC connections must be made to the UPS module before attaching Liebert EXM TXC to UPS module. Liebert EXM TXC’s must attach to the right side only of the Liebert EXM UPS.
  • Page 14: Bolting Cabinets Together

    Liebert EXM TXC OLTING ABINETS OGETHER NOTE UPS wiring must be completed before the cabinets are bolted together. Line up cabinets so that mounting holes are aligned. ® ™ ™ Vertiv | Liebert User Manual |...
  • Page 15: Figure 3 Bolting Liebert Exm Ups To A Liebert Exm Txc

    • Installing four eyebolts in the factory-fabricated holes, one at each corner of the unit, attaching cables or similar strapping to the eyebolts and lifting with a suitable mechanism. • Placing suitable straps on the Liebert EXM TXC. The straps must go under the unit to be lifted. ®...
  • Page 16: Floor Installation

    1.3.1 Floor Installation If the Liebert EXM TXC is to be placed on a raised floor, the UPS should be mounted on a pedestal that will support the equipment point loading. Refer to the Liebert EXM UPS manual, SL-25648 or SL-25650, to design this pedestal.
  • Page 17: Figure 4 Cabinet Arrangement

    Cabinet Cabinet Cabinet Liebert EXM UPS connected Liebert EXM UPS connected to Liebert EXM TXC and Battery Cabinets an to Liebert EXM TXC and Maintenance Maintenance Bypass Cabinet Bypass Cabinet (TXC must be on right side of the Liebert EXM)
  • Page 18: Installation Drawings

    Installation Drawings 2.0 INSTALLATION DRAWINGS Figure 6 Liebert EXM TXC Main components Neutral Transformers Busbar Ground Busbar EXM15010 FRONT FRONT RIGHT SIDE Rev. 1 With Cover Door Removed Panel Removed ® ™ ™ Vertiv | Liebert User Manual |...
  • Page 19: Figure 7 Busbars-Liebert Exm Txc

    3. All wiring is to be in accordance with national and local electrical codes. 4. If maintenance bypass cabinet is attached (See Detail A) to UPS, the Vertiv will suppy the interconnection cables. 5. 225A panelboard for 10k - 40kVA only. Transformer 400A panelboard for 60k - 100kVA only.
  • Page 20: Figure 8 Lineup Arrangement, Liebert Exm With Liebert Exm Txc, 10-40Kva

    Installation Drawings Figure 8 Lineup arrangement, Liebert EXM with Liebert EXM TXC, 10-40kVA 55.1" (1400mm) 7.9" (200mm) 23.6" 23.6" (600mm) (600mm) Notes 1. All dimensions are in inches (mm). 2. 24" (610) minimum clearance above unit for air exhaust 36" (914) front access required for service.
  • Page 21: Figure 10 Outline Drawing, Liebert Exm Txc For Liebert Exm, 10-100Kva

    Installation Drawings Figure 10 Outline drawing, Liebert EXM TXC for Liebert EXM, 10-100kVA 20.4" (519mm) 15.3" See Detail A (387mm) Leveler 34.5" (876mm) Ventilation 28.3" (718mm) Caster DETAIL A BOTTOM 24" (608mm) Notes 39.8" (1010mm) 23.6" 1. 24" [610] minimum clearance above unit for (600mm) air exhaust.
  • Page 22: Figure 11 Liebert Exm Txc Transformer Location

    Installation Drawings Figure 11 Liebert EXM TXC transformer location Transformer, T1 Transformer, T2 RIGHT SIDE REAR OF CABINET ® ™ ™ Vertiv | Liebert User Manual |...
  • Page 23: Figure 12 Bend Radius - Top Feed Power Connections, 10-100Kva System

    Figure 12 Bend radius - Top feed power connections, 10-100kVA system NOTE Interconnection wiring between the UPS and bypass distribution cabinet is supplied by Vertiv when the Liebert EXM TXC and Liebert EXM UPS are ordered as a system. Table 2 Hardware torque values...
  • Page 24: Specifications

    Maximum Altitude Above MSL, ft 1% Maximum kW derate / 100m rise between 1500- 3000m Table 4 Liebert EXM TXC, 10-100k, mechanical characteristics Mechanical Characteristics Values Dimensions, W x D x H, in (mm) 23.625 x 39.375 x 78.75 (600 x 1000 x 2000)
  • Page 25: Table 5 Liebert Exm Txc Heat Dissipation, Both Transformers, Full Load

    Specifications Table 5 Liebert EXM TXC heat dissipation, both transformers, full load Liebert EXM Heat Liebert EXM Heat Dissipation Heat Dissipation Heat Dissipation Dissipation TXC Rating, 208:208 Transformer 220:220 Transformer 480:208 Transformer 600:208 Transformer BTU/Hr (kW) BTU/Hr (kW) BTU/Hr (kW) BTU/Hr (kW) 3992 (1.152)
  • Page 26: Table 8 Terminal Block Torque With Compression Lugs For Control Wiring

    Torque AWG Wire Size or Lb-in Range (Nm) 3.5 to 5.3 #22 - #14 (0.4 to 0.6) NOTE Refer to the manufacturer’s data for proper torque for circuit breaker power connections. ® ™ ™ Vertiv | Liebert User Manual |...
  • Page 27: Table 9 Electrical Data-Liebert Exm Txc, 480Vac Input, 208Vac Output, Rectifier Input

    Specifications Table 9 Electrical data—Liebert EXM TXC, 480VAC input, 208VAC output, rectifier input, with 480V:208V transformer Maximum Liebert EXM Rectifier Recommended 75°C Wire Input Upstream Current A Copper Aluminum Rating, kVA Current, A Phase Protection, A Total Wire Wire Bolt Size...
  • Page 28: Table 12

    (1) #1 (1) 1/0 3W + G (1) 1/0 (1) 3/0 See Notes on Tables on page 25. Table 13 Electrical data—Liebert EXM TXC, 208VAC or 220VAC input, rectifier input, with 208V:208V or 220V:220V transformer 75°C Maximum Recommend Wire Liebert EXM...
  • Page 29: Table 15 Liebert Exm Txc Inrush Multiplier

    Specifications Table 14 Electrical data—Liebert EXM TXC, 208VAC or 220VAC input, bypass input, with 208V:208V or 220V:220V transformer 75°C Maximum Recommend Wire Liebert EXM System Current Input Upstream Copper Aluminum Bolt Rating, kVA Current, A Phase Protection, A Total Wire...
  • Page 30 Specifications ® ™ ™ Vertiv | Liebert User Manual |...
  • Page 32 © 2018 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co.