Setting Teamwork Control Parameters - Huawei NetCol8000-A Series User Manual

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A Series:
Table of Contents

Advertisement

NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
Follow-up Procedure
After a USB flash drive has been inserted into the controller USB port and successfully
identified, tap Export File under MIB File to export the MIB file to the USB flash drive for
the customer's use in accessing a third-party EMS.
Before using a USB flash drive, ensure that its data has been scanned by antivirus software
and is secure.
Figure 5-18 Exporting an MIB file successfully

5.4.7 Setting Teamwork Control Parameters

Prerequisites
Assign teamwork group number and teamwork unit address for the teamwork controlled
smart cooling products as follows:
Context
Issue 10 (2019-01-15)
Teamwork group no.: Group the smart cooling products in adjacent areas as one, that is,
assign one teamwork control number for them. At most four teamwork control groups
can be assigned (1–4).
Teamwork unit address: The address for the smart cooling product in the same group
cannot be the same (address range: 1–32). The smart cooling product addressed 1 is the
master one that collects, processes, and delivers data. Set the unit address numbers from
one to the Total number of units in this group.
The parameters in this section are for reference only. Set actually parameter values as
required.
To change teamwork settings, log in as the Admin or Engineer user.
Copyright © Huawei Technologies Co., Ltd.
5 ACC Introduction
Figure 5-18
shows successful file export.
100