Burkert 8605 Quick Start Manual page 8

Digital control electronics for solenoid valves
Table of Contents

Advertisement

Shield
12...24 V
Fig. 3:
Plug-in connector connection, digital
Fig. 4:
Connection input PCB
Pin
Assignment
1
24 V DC
2
DI2 (digital input, fre-
quency input)
Tab. 1:
Pin assignment of the input PCB
8
CAN_H
CAN_L
GND
4
1
Pin
Assignment
3
GND
4
AI1/DI1 (analog input,
digital input)
english
6.2 Mounting the control electronics
Screw M3
Cover
Fig. 5:
Mounting the control electronics on the valve
When screwing the cable plug to the valve, ensure that the seal
is seated correctly.
NOTE
Damage to the device.
Excessive tightening torque will deform the cable plug.
▶ Screw on screw M3 to a tightening torque of 0.3 Nm.
Seal
Cable plug
Seal