8.12
Function "simulation value" (066)
8.13
Function "output current" (067), HART only
Displays the output current in mA.
Caution!
This function is available for HART devices only!
8.14
Function "2nd cyclic value" (067),
PROFIBUS PA only
Selects the second cyclical value.
• height/dist.
Levelflex always transmits the distance as the second cyclical value.
Caution!
This function is available for PROFIBUS PA devices only!
8.15
Function "4mA value" (068), HART only
In this function, enter the level (or volume, weight) at which the output current should be 4 mA.
This entry is only required if you selected the "current turn down" option in the "curr. output
mode" (063) function.
After selecting the "sim. level" option in the
"simulation" (065) function, the following message
appears in the display: you can enter the level.
After selecting the "sim. volume" option in the
"simulation" (065) function, the following message
appears in the display: you can enter the volume.
After selecting the "sim. current" option in the
"simulation" (065) function, the following message
appears in the display: Enter the output current (only for
HART instruments).