Levelflex M
⇒
ENDRESS + HAUSER
–
+
E
⇒
ENDRESS + HAUSER
–
+
E
⇒
ENDRESS + HAUSER
–
+
E
Endress+Hauser
5.3
Function "probe" (032)
Use this function to select whether the probe is at the time of the commisioning uncovered or cov-
ered. If the probe is uncovered, the Levelflex can determine the probe length automatically
"determine length" (034). function. If the probe is covered, a correct entry is required in the
"probe length" (033) function
Selection:
• free
• covered
5.4
Function "probe length" (033)
Use this function to enter the probe length.
5.5
Function "determine length" (034)
Use this function to determine the probe length automatically.
Due to the mounting conditions, the automatically determined probe length may be larger than the
actual probe (typically 20 .. 30 mm longer). This has no influence on the measuring accuracy. When
entering the empty value for a linerisation, please use the "empty calibration" instead of the auto-
matically determined probe length.
Selection:
• length ok
• too short
• too long
After selecting "length too short" or "length too long" the calculation of the new probe length takes
up to approx. 10 s.
5 Function group "length adjustment" (03)
33
Need help?
Do you have a question about the Levelflex M FMP40 and is the answer not in the manual?