Function "Fixed Cur. Value" (064), Hart Only; Function "Out Status" (064), Profibus Pa Only - Endress+Hauser Levelflex M FMP40 Function Manual

Guided level-radar with hart, profibus pa and foundation fieldbus
Hide thumbs Also See for Levelflex M FMP40:
Table of Contents

Advertisement

8 Function group "output" (06), - "PROFIBUS param." (06), PROFIBUS PA only
ENDRESS + HAUSER
+
E
"
ENDRESS + HAUSER
+
E
"
52
8.9

Function "fixed cur. value" (064), HART only

Set the fixed current value with this function. This data is necessary if you have selected the "fixed
current" option in the "curr. output mode" (063) function.
User input:
3,8...20,5 mA
Caution!
This user input is available for HART devices only!
8.10

Function "out status" (064), PROFIBUS PA only

Displays the current output status (for value, see operating instructions of relevant instrument).
Caution!
This function is available for PROFIBUS PA devices only!
Levelflex M
Endress+Hauser