Function "Low Output Limit" (062), Hart Only; Function "Set Unit To Bus" (062), Profibus Pa Only - Endress+Hauser Levelflex M FMP40 Function Manual

Guided level-radar with hart, profibus pa and foundation fieldbus
Hide thumbs Also See for Levelflex M FMP40:
Table of Contents

Advertisement

8 Function group "output" (06), - "PROFIBUS param." (06), PROFIBUS PA only
ENDRESS + HAUSER
+
E
"
ENDRESS + HAUSER
+
E
"
50
8.5

Function "low output limit" (062), HART only

The output of negative level values can be suppressed with this function.
Selection:
• off
minimum output -10% (3.8 mA for HART)
• on
minimum output 0% (4 mA for HART)
Caution!
This user input is available for HART devices only!
8.6

Function "set unit to bus" (062), PROFIBUS PA only

• confirm
After confirming this function, the unit of the measured variable is taken over in
the AI block (PV scale -> Out scale).
This function must always be executed after changing the unit.
Caution!
This function is available for PROFIBUS PA devices only!