8 Function group "output" (06), - "PROFIBUS param." (06), PROFIBUS PA only
⇒
ENDRESS + HAUSER
–
+
E
"
⇒
ENDRESS + HAUSER
–
+
E
"
50
8.5
Function "low output limit" (062), HART only
The output of negative level values can be suppressed with this function.
Selection:
• off
minimum output -10% (3.8 mA for HART)
• on
minimum output 0% (4 mA for HART)
Caution!
This user input is available for HART devices only!
8.6
Function "set unit to bus" (062), PROFIBUS PA only
• confirm
After confirming this function, the unit of the measured variable is taken over in
the AI block (PV scale -> Out scale).
This function must always be executed after changing the unit.
Caution!
This function is available for PROFIBUS PA devices only!