FINAL CHECKS BEFORE WALKING AWAY . . .

So that the S&C Micro-AT Source-Transfer Control is
ready for automatic operation, make sure that both
source voltage indicating lamps and the automatic-trans-
fer "ready" indicating lamp are illuminated. If the
"READY" lamp is not lighted, refer to the liquid-crystal
display on the faceplate of the Micro-AT control. When
not being used to show menu information, this display
shows messages explaining why the lamp is not lighted.
NOTE: A lighted "READY" lamp indicates that the
status of associated components is normal, but an
absence of illumination does not necessarily mean that
s
S&C ELECTRIC COMPANY
the control is inoperative. For example, when transfer
to the alternate source occurs, the lamp extinguishes
but the control is ready for any subsequent pro-
grammed automatic operation required by a change in
source conditions. Likewise, if the stored-energy opera-
tors are decoupled, the "READY" lamp is extin-
guished—and the switches will not operate—but the
control is fully operative.
Close and padlock the access doors to the low-voltage
control compartment and high-voltage compartments.