S&C PMH Instructions For Operation Manual

Source-transfer pad-mounted gear
Hide thumbs Also See for PMH:

Advertisement

Quick Links

S&C Source-Transfer PMH Pad-Mounted Gear
Outdoor Distribution (14.4 kv and 25 kv)
This publication contains instructions for operation of fuses and Mini-Rupter
Source-Transfer PMH Pad-Mounted Gear. For instructions regarding field programming and
operation of the S&C Micro-AT Source-Transfer Control, refer to S&C Instruction Sheet 515-500.
For operating instructions regarding the optional test-panel feature (Catalog Number Suffix "-Y5"),
if furnished, refer to S&C Instruction Sheet 515-505.

TABLE OF CONTENTS

Section
Qualified Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Understanding Safety-Alert Messages . . . . . . . . . . . . . . . . . . . . 3
Following Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Replacement Instructions and Labels . . . . . . . . . . . . . . . . . . . . 3
SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
OPERATING DESCRIPTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Decoupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Automatic Switch Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Nonautomatic Switch Operation . . . . . . . . . . . . . . . . . . . . . . . . 11
Charging Operator (Nonelectrical) . . . . . . . . . . . . . . . . . . . . . . 11
Front Barriers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Assembling the Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Installing the Fuse in the Mounting. . . . . . . . . . . . . . . . . . . . . . 15
Installing and Closing the Fuse . . . . . . . . . . . . . . . . . . . . . . . . . 16
A Note on Single-Pole Switching . . . . . . . . . . . . . . . . . . . . . . . . 20
Opening and Removing the Fuse. . . . . . . . . . . . . . . . . . . . . . . . 20
Supersedes Instruction Sheet 663-503 dated 9-20-93
s
S&C ELECTRIC COMPANY
INSTRUCTIONS
For Operation
Page Number
c
1995
With Micro-AT
Section
How to Detect and Replace a Blown Fuse. . . . . . . . . . . . . . . . 23
Installing the Fuse in the Mounting. . . . . . . . . . . . . . . . . . . . . . 24
FINAL CHECKS BEFORE WALKING AWAY. . . . . . . . . . . . . . . . 25
IF OPERATOR STALLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Returning Equipment to Service . . . . . . . . . . . . . . . . . . . . . . . . 28
Enclosure Finish . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
APPENDIX A
Dielectric Testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
APPENDIX C
Ratings for S&C Mini-Rupter Switches. . . . . . . . . . . . . . . . . . . 29
APPENDIX D
Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
APPENDIX E
S&C PMH Pad-Mounted Gear . . . . . . . . . . . . . . . . . . . . . . . . . 34
INSTRUCTION SHEET
®
Control
®
Switches in S&C
Page Number
663-503
Page 1 of 35
August 14, 1995

Advertisement

Table of Contents
loading

Summary of Contents for S&C PMH

  • Page 1: Table Of Contents

    SWITCHING WITH UNI-RUPTER S&C PMH Pad-Mounted Gear ......34 Installing and Closing the Fuse ......16 A Note on Single-Pole Switching .
  • Page 2: Introduction

    Refer to Appendix D for descriptions of the optional features. These instructions are for operation of fuses and Mini- Rupter Switches in S&C Pad-Mounted Gear, Source-Trans- fer PMH Models equipped with the S&C Micro-AT Source- 663-503 INSTRUCTION SHEET Page 2 of 35 August 14, 1995 S&C ELECTRIC COMPANY...
  • Page 3: Safety Information

    There are several types of safety-alert messages which Ç NOTICE may appear throughout this instruction sheet as well as on labels affixed to the S&C Source-Transfer PMH Pad- Thoroughly and carefully Mounted Gear. Familiarize yourself with these types of read this instruction sheet messages and the importance of the various signal words, before operating your S&C...
  • Page 4: Safety Precautions

    S&C Source-Transfer PMH Pad-Mounted Gear ® With Micro-AT Control Outdoor Distribution (14.4 kv and 25 kv) SAFETY PRECAUTIONS Ç DANGER Pad-mounted gear contains high voltage. Failure to observe the precautions below will result in serious injury or death. Some of these precautions may differ from company operating procedures and rules.
  • Page 5: Operating Description

    SAFETY PRECAUTIONS — Continued Ç DANGER — Continued Pad-mounted gear contains high voltage. Failure to observe the precautions below will result in serious injury or death. Some of these precautions may differ from company operating procedures and rules. Where a discrepancy exists, users should follow their company’s operating procedures and rules.
  • Page 6: Components

    S&C Source-Transfer PMH Pad-Mounted Gear ® With Micro-AT Control Outdoor Distribution (14.4 kv and 25 kv) COMPONENTS Figures 1 through 4 which follow illustrate many of the of the instructions, it is recommended that these figures basic components and features of S&C Source-Transfer be reviewed to gain familiarity with the various compo- Pad-Mounted Gear.
  • Page 7 COMPONENTS — Continued Right source voltage Left source voltage indicating lamp indicating lamp Manual/automatic operation selector switch. When in Automatic-transfer “MANUAL,” prevents an “ready” indicating lamp automatic source transfer while permitting manual operation using open/close pushbuttons Overcurrent-lockout indicating lamp and reset key (furnished with optional overcurrent- lockout feature, Catalog Number Two-line...
  • Page 8 S&C Source-Transfer PMH Pad-Mounted Gear ® With Micro-AT Control Outdoor Distribution (14.4 kv and 25 kv) COMPONENTS — Continued Remote-indication wiring provided with optional remote- indication feature (Catalog Number Suffix “-Y4”), leads to a terminal block for user’s connections Supervisory control wiring...
  • Page 9 COMPONENTS — Continued Left-hand door retainer—rotate latch Viewing window for visible verifica- upward to open door. To secure left-hand tion of switch position is removable door closed, rotate latch downward over for phasing. To remove window, stop mounted on outer edge of door loosen wing-head screws and lift S&C Uni-Rupter Dual-purpose...
  • Page 10: Mini-Rupter Switches

    S&C Source-Transfer PMH Pad-Mounted Gear ® With Micro-AT Control Outdoor Distribution (14.4 kv and 25 kv) MINI-RUPTER SWITCHES Ç WARNING 1. To prevent an automatic operation when decoupling Mini-Rupter Switch. Upon completion of an open- or coupling an operator to a switch, during manual...
  • Page 11: Automatic Switch Operation

    MINI-RUPTER SWITCHES — Continued Automatic Switch Operation when voltage is present on the associated source. The charging operation takes approximately 25 seconds. High-speed quick-make quick-break operation is provided by stored-energy operators which, when solenoid tripped If Control Power Is Lost and Operator Is Charged: in response to control signals from the S&C Micro-AT To manually operate the stored-energy operator’s quick- Source-Transfer Control, automatically open and close...
  • Page 12: Front Barriers

    S&C Source-Transfer PMH Pad-Mounted Gear ® With Micro-AT Control Outdoor Distribution (14.4 kv and 25 kv) MINI-RUPTER SWITCHES — Continued selector is in the “CHARGING POSITION,” the control Ç DANGER circuit is disconnected to prevent manual or automatic When working in the high-voltage compartments,...
  • Page 13 MINI-RUPTER SWITCHES — Continued If the Mini-Rupter Switch is closed with the front bar- Ç WARNING rier in the “slide-in” position, the switch blades will be Do not leave dual-purpose front barriers in the “slide-in” blocked and the stored-energy operator will stall in a par- position for more than one week.
  • Page 14 S&C Source-Transfer PMH Pad-Mounted Gear ® With Micro-AT Control Outdoor Distribution (14.4 kv and 25 kv) MINI-RUPTER SWITCHES — Continued Figure 11. Alternate method of replacing front barrier using Grappler. Inset shows barrier being supported on Grappler prongs. 663-503 INSTRUCTION SHEET...
  • Page 15: Fusing

    FUSING S&C Source-Transfer PMH Pad-Mounted Gear is fur- Installing the Fuse in the Mounting nished with S&C Fuse Mountings with Uni-Rupter that Follow the instructions found under “Installing and Clos- accommodate S&C Type SML-20 Power Fuses, S&C Type ing the Fuse” on pages 16 through 19.
  • Page 16: Switching With Uni-Rupter

    S&C Source-Transfer PMH Pad-Mounted Gear ® With Micro-AT Control Outdoor Distribution (14.4 kv and 25 kv) SWITCHING WITH UNI-RUPTER Installing and Closing the Fuse Then remove only the dual-purpose front barrier associated with the fuse mounting into which the fuse Before proceeding with the instructions on installing is to be installed.
  • Page 17 SWITCHING WITH UNI-RUPTER — Continued 3. For all fuses except 25-kv Fault Fiter Electronic 4. For 25-kv Fault Fiter Electronic Power Fuses, de- Power Fuses, install a fuse into its hinge as follows: energize, test, and properly ground the mounting in accordance with safe operating procedures and rules, (a) Position the Grappler cone in the fuse pull ring and and then install the fuse into its mounting by hand...
  • Page 18 S&C Source-Transfer PMH Pad-Mounted Gear ® With Micro-AT Control Outdoor Distribution (14.4 kv and 25 kv) SWITCHING WITH UNI-RUPTER — Continued 5. Use the Grappler to remove the dual-purpose front bar- 6. With the Grappler prongs pointed downward, insert the rier from the “slide-in”...
  • Page 19 SWITCHING WITH UNI-RUPTER — Continued Figure 18. Closing the fuse. Inset on right shows close-up of Grappler in position to close the fuse. Top inset shows close-up of Uni-Rupter with the fuse fully closed. INSTRUCTION SHEET 663-503 Page 19 of 35 August 14, 1995 S&C ELECTRIC COMPANY...
  • Page 20: A Note On Single-Pole Switching

    S&C Source-Transfer PMH Pad-Mounted Gear ® With Micro-AT Control Outdoor Distribution (14.4 kv and 25 kv) SWITCHING WITH UNI-RUPTER — Continued Ç WARNING A Note on Single-Pole Switching operating voltage exceeds 22 kv. Single-pole switch- ing should be performed only if each phase is car-...
  • Page 21 SWITCHING WITH UNI-RUPTER — Continued 4. Pull the fuse vigorously through its full travel without Ç NOTICE hesitation at any point. See Figure 20. A downward force should be maintained on the universal pole Do not close a door on a fuse in the open position. The door will strike the fuse pull ring which will inter- through the fuse-opening operation to counteract any fere with door closing.
  • Page 22 S&C Source-Transfer PMH Pad-Mounted Gear ® With Micro-AT Control Outdoor Distribution (14.4 kv and 25 kv) SWITCHING WITH UNI-RUPTER — Continued 7. For all fuses except 25-kv Fault Fiter Electronic Power 8. For 25-kv Fault Fiter Electronic Power Fuses, de-...
  • Page 23: Re-Fusing

    RE-FUSING How to Detect and easy to check the fuse condition with the fuse in the closed position. The blown-fuse target retracts within Replace a Blown Fuse the end fitting or holder when the blown fuse unit or Open the appropriate fuse-compartment door and secure interrupting module is replaced.
  • Page 24: Installing The Fuse In The Mounting

    SML-20 Power Fuse SML-4Z Power Fuse Fault Fiter Electronic Power Fuse Figure 24. Blown-fuse target locations for the fuse types used in PMH models of S&C Pad-Mounted Gear. 663-503 INSTRUCTION SHEET Page 24 of 35 August 14, 1995...
  • Page 25: Final Checks Before Walking Away

    FINAL CHECKS BEFORE WALKING AWAY . . . So that the S&C Micro-AT Source-Transfer Control is the control is inoperative. For example, when transfer ready for automatic operation, make sure that both to the alternate source occurs, the lamp extinguishes source voltage indicating lamps and the automatic-trans- but the control is ready for any subsequent pro- fer “ready”...
  • Page 26: If Operator Stalls

    S&C Source-Transfer PMH Pad-Mounted Gear ® With Micro-AT Control Outdoor Distribution (14.4 kv and 25 kv) IF OPERATOR STALLS . . . The stored-energy operator’s quick-make quick-break Restore the stored-energy operator to a normal mechanism will stall in a partially discharged state if the...
  • Page 27: Maintenance

    MAINTENANCE Components Ç DANGER No routine maintenance is required for the S&C Micro-AT When access to high-voltage compartments is required Source-Transfer Control. However, operational testing for inspection, service, or repairs, always observe the once per year in accordance with S&C Instruction Sheet precautions below.
  • Page 28: Returning Equipment To Service

    The responsibility for ensuring that a finish protects the procedures should be observed: enclosure lies with both the manufacturer and the user. S&C Source-Transfer PMH Pad-Mounted Gear is finished 1. Make sure that switch and fuse grounding means are with the S&C Ultradur™ Finishing System, which pro- removed and that dual-purpose front barriers are vides lasting protection for the enclosure.
  • Page 29: Preliminary Tryout Before Gear Is Energized-Optional

    S&C Sales Complete ratings for Mini-Rupters as applied in S&C Office. The two-time duty-cycle fault-closing ratings Source-Transfer PMH Pad-Mounted Gear are shown in the shown for Mini-Rupters define the ability to close the table below. In addition to the load-dropping ratings...
  • Page 30: Ratings For S&C Power Fuses With Uni-Rupter

    Complete ratings and capabilities of S&C Power Fuses systems of these voltage ratings. The duty-cycle fault-clos- with Uni-Rupter as applied in S&C Source-Transfer PMH ing capabilities shown for S&C Power Fuses with Uni- Pad-Mounted Gear are shown in the table below. Uni-...
  • Page 31: Optional Features

    APPENDIX D OPTIONAL FEATURES Suffix Added to Applicable to Item Pad-Mounted Gear Models Catalog Number Light Gray Outdoor Ultradur Finish instead of olive green With olive green finish -A10 Stainless-Steel Enclosure With light gray finish -A12 For use except when option suffix “-F2” is specified Hexhead Actuator for use in lieu of pentahead actuator on all Penta-Latch Mechanisms...
  • Page 32 S&C Source-Transfer PMH Pad-Mounted Gear ® With Micro-AT Control Outdoor Distribution (14.4 kv and 25 kv) APPENDIX D — Continued OPTIONAL FEATURES—Continued Suffix Added to Applicable to Item Pad-Mounted Gear Models Catalog Number Switch-Terminal Adapters—for connection of two cables (through 750 kc mil) per terminal Note: Space limitations prevent use of these adapters where surge arresters are to be installed In switch compartments.
  • Page 33: Accessories

    APPENDIX D — Continued ACCESSORIES Item Catalog Number S&C Test Accessory, permits preliminary checkout of source-transfer control using single-phase 120-volt ac source (before medium-voltage connections are made to the pad-mounted gear) to expedite full service once medium voltage is available. The test TA-1316 accessory isolates the S&C Voltage Sensor during testing and eliminates the possibility of backfeed during test procedures Portable Remote-Control Station with 50-foot cord, connects to one remote-control receptacle (not included;...
  • Page 34: Current-Limiting Fuses For Use In

    14.4 kv nominal, 17.0 kv maximum, and 200 amperes maximum. S&C Holders for use in 25-kv models of PMH Pad-Mounted Gear are rated The maximum voltage and maximum ampere ratings listed in this 25 kv nominal, 29 kv maximum, and 200 amperes maximum.
  • Page 35 APPENDIX E — Continued • Recommended Voltage Ratings Protection of single-phase transformers serving single- phase loads. In general, current-limiting fuses should have a maximum voltage rating equal to, but not greater than 140% of, the • Protection of three-phase lateral circuits fed by single- system line-to-line voltage since, for most applications, conductor shielded cable (provided each transformer the fuses can be exposed to full system line-to-line voltage...