GE Kelman TRANSFIX 1.6 Installation Manual page 38

Transformer oil dissolved gas and moisture monitor
Table of Contents

Advertisement

C.3
Pre-Installation Photographs
It is recommended that photographs of the installation site be taken in advance of the
installation in order to properly assess the site, aid in planning the installation and
contribute to the Short Duration Safety Plan. The following areas should be
photographed:
C.3.1 Valves / Plumbing:
 Proposed Supply valve location
 Proposed Return valve location
 Alternative Supply valve location
 Alternative Return valve location
 Secondary Shut-Off valve location (if needed)
 Oil supply & return routing (the ¼ in. stainless steel tubing)
C.3.2 Proposed Product location:
 Overview from front
 Overview from left side
 Overview from back
 Overview from right side
C.3.3 Proposed Cable routing and connection locations:
 Communication cable routing (include terminations)
 Power cable routing (include terminations)
C.3.4 Transformer:
 Nameplate photo
 Oil temperature gauge
 Oil level gauge
 Control panel with door open
 Overview of each side
 Cooling loop(s)
 Conservator with close-ups of gauges
 Pumps
 Desiccant
 Nitrogen Cylinder / Regulator gauges (if transformer is nitrogen-blanketed) (both
Output & Cylinder psig)
MA-001 – TRANSFIX-family Installation Manual – Rev 3.0
18-Jan-16
Page 38 of 55