I.L. 70C1036H05
Appendix D - Display Menu Diagrams Continued
Appendix D - Page D-25
CURRENT Protection
LSIG Current Curve
LONG SLOPE
LONG PU
LONG TIME
LONG MEMORY
SHORT SLOPE ***
SHORT PU
SHORT TIME
INST PU
GROUND PU**
GROUND SLOPE****
GROUND TIME****
EXT GND CT RATIO**
NEUTRAL PROTECT*
AMP UNBALANCE
AMP UNBALANCE (time)
PHASE LOSS
VOLTAGE Protection
DISPLAY (6 active)
IA IB IC
IN IG
L-L VOLTAGE
FwdPower
PF Hz
ENERGY FWD & REV
(all others)
AuxReLaYs
All relays DISABLED
ALARMS
All alarms OFF
ACC BUS
Address1 Relay1 is Aux.-Aux Switch
All other addresses and relays OFF
SYSTEM
FIXED DEMAND 15 Min window
WAVEFORM CAPTURE OFF
FREQ
Relay B,C MANUAL
1. Except LSIA will have Ground Alarm on @ .40x
2. Plug ratings 3200, 4000, 5000, 6300 A are set to .24
Effective 10/2004
Courtesy of NationalSwitchgear.com
LSIG ON
PHASE SLOPE
I2T
Pickup
1.00
PHASE TimeDial
4.0 s
SHORT PU
ON
SHORT TIME
FLAT
INST PU
3.0
GROUND PU**
0.30 s
GROUND SLOPE****
4.0
2
GROUND TIME****
0.40
EXT GND CT RATIO**
FLAT
NEUTRAL PROTECT*
0.30 s
AMP UNBALANCE
none
AMP UNBALANCE (time)
100%
PHASE LOSS
OFF
10 s
*
Applicable on LSI or IEC factory styles only
OFF
** Applicable on LSIG, LSIA and IEC-EF
*** Only available on LSIG, LSI, LSIA Current Curve. On IEEE curve and IEC
DISABLED *****
curve, LONG MEMORY and SHORT I
**** Applicable on LSIG, IEC-EF
***** VOLTAGE PROT and FREQ settings available on Cat #11PXXX
AUTO
ON
ON
ON
ON
INCOM
ON
OFF
INCOM ADDRESS
INCOM BAUD RATE
1
EXT COMM OpenTrip
EXT COMM
60Hz
EXT COMM CLOSE
DT 910 COMM
IEEE Curve
PHASE SLOPE
MOD INV
Pickup
1.00
PHASE TimeDial
2.0
SHORT PU
3.0
SHORT TIME
0.30 s
INST PU
4.0
EARTH PU**
2
0.40
EARTH SLOPE****
FLAT
EARTH TIME****
0.30 s
EXT EARTH CT RATIO**
none
NEUTRAL PROTECT*
100%
AMP UNBALANCE
OFF
AMP UNBALANCE (time)
10 s
PHASE LOSS
OFF
100 hex
9600
ENABLED
TRIP
ENABLED
DISABLED
Factory
Settings
IEC Curve
IEC - A
1.00
0.20
3.0
0.30 s
4.0
0.40
FLAT
0.30 s
none
100%
OFF
10 s
OFF
2
T SLOPE settings are not available.
only.
TEST
PH TEST
GND TEST
Page 75