Remove Failed Controller - Fujitsu ETERNUS AB Series Hardware Maintenance Manual

Hide thumbs Also See for ETERNUS AB Series:
Table of Contents

Advertisement

Procedure
1. Unpack the new controller canister, and set it on a flat, static-free surface.
Save the packing materials to use when shipping the failed controller canister.
2. Locate the MAC address and FRU part number labels on the back of the controller canister.
3. From SANtricity System Manager, locate the replacement part number for the controller canister you are
replacing.
When a controller has a fault and needs to be replaced, the replacement part number is displayed in the
Details area of the Recovery Guru. If you need to find this number manually, follow these steps:
a) Select Hardware.
b) Locate the controller shelf, which is marked with the controller icon .
c) Click the controller icon.
d) Select the controller, and click Next.
e) On the Base tab, make a note of the Replacement Part Number for the controller.
4. Confirm that the replacement part number for the failed controller is the same as the FRU part number for
the replacement controller.
Attention: Possible loss of data access – If the two part numbers are not the same, do not
attempt this procedure. In addition, if the failed controller canister includes a host interface card
(HIC), you must install that HIC into the new controller canister. The presence of mismatched
controllers or HICs causes the new controller to lock down when you bring it online.
5. Back up the storage array's configuration database.
If a problem occurs when you remove a controller, you can use the saved file to restore your configuration.
a) In System Manager, navigate to the support page.
b) Select the Support Center tab.
c) Select Diagnostics tab.
d) Select the Collect Support Data.
6. If the controller is not already offline, take it offline now using SANtricity System Manager.
• a. Select Hardware.
b. If the graphic shows the drives, select Show back of shelf to show the controllers.
c. Select the controller that you want to place offline.
d. From the context menu, select Place offline, and confirm that you want to perform the operation.
Note: If you are accessing SANtricity System Manager using the controller you are attempting to take
offline, a SANtricity System Manager Unavailable message is displayed. Select Connect to an alternate
network connection to automatically access SANtricity System Manager using the other controller.
7. Wait for SANtricity System Manager to update the controller's status to offline.
Attention: Do not begin any other operations until after the status has been updated.
8. Select Recheck from the Recovery Guru, and confirm that the OK to remove field in the Details area
displays Yes, indicating that it is safe to remove this component.
What to do next
Go to
Remove failed

Remove failed controller

You remove a controller canister to replace the failed canister with a new one. You remove the failed controller
canister by removing the controller from the controller shelf and removing the battery, host interface card,
power supply, DIMMs, and fans.
Remove controller canister
You remove the failed controller canister so you can replace it with a new one. Disconnect all the cables then
you can slide the controller out of the controller shelf.
controller.