System Maintenance
Fan Shaft Bearings
Compatibility of grease is critical. Relubricatable Browning
bearings are supplied with grease fittings or zerks for ease of
lubrication with hand or automatic grease guns. Always wipe
the fitting and grease nozzle clean.
For safety, stop rotating equipment. Add one half of the
recommended amount shown in Table 19. Start bearing,
and run for a few minutes. Stop bearing and add the second
half of the recommended amount. A temperature rise,
sometimes 30°F (1°C), after relubrication is normal. Bearing
should operate at temperature less than 200°F (94°C) and
should not exceed 225°F (107°C) for intermittent operation.
For a relubrication schedule, see Table 17. For any
applications that are not in the ranges of the table, contact
McQuay.
The tables below state general lubrication
recommendations based on our experience and are
intended as suggested or starting points only. For best
results, specific applications should be monitored regularly
and lubrication intervals and amounts adjusted accordingly.
Table 17: SAF and RAF Relubrication Intervals
(Use NLGI #2 Lithium or Lithium Complex Grease)
Speed
Temperature
100 rpm
Up to 120°F
(50°C)
500 rpm
Up to 150°F
(65°C)
1000 rpm
Up to 210°F
(100°C)
1500 rpm
Over 210°F
(100°C) to
250°F (120°C)
Above 1500 rpm
Up to 150°F
(65°C)
Max catalog rating
Over 150°F
(65°C) to 250°F
(120°C)
Above 250°F
(120°C)
46
CAUTION
CAUTION
Cleanliness
Relub. intervals
Clean
6 to 12 months
Clean
2 to 6 months
Clean
2 weeks to 2
months
Clean
Weekly
Dirty/wet
1 seek to 1 month
Dirty/wet
Daily to 2 weeks
Contact Browning
Table 18: Recommended Lubricants for Fan Shaft Ball
Bearings
Name
Temperature
Texaco,
30° to 350°F
Premium RB
(34° to 177°C)
Mobile, AW2
40° to 437°F
(40° to 175°C)
Mobile, SHC
68° to 356°F
100
(50° to 180°C)
Chevron,
60° to 450°F
Altiplex
(51° to 232°C)
Synthetic
Exxon, ronex
40° to 300°F
MP
(40° to 149°C)
Note: Temperature ranges over 140°F are shown for lubricants only.
Maximum unit temperature is 140°F.
Table 19: Recommended SAF and RAF Relubrication
Grease Charge
Shaft Size (in)
OZ.
1/2 to 3/4
0.03
7/8 to 1-3/16
0.10
1-1/4 to 1-1/2
0.15
1-11/16 to 1-15/16
0.20
2 to 2-7/16
0.30
2-1/2 to 2-15/16
0.50
3 to 3-7/16
0.85
3-1/2 to 4
1.50
Bearing Replacement
The following instructions must be read in entirety before
attempting installation or removal. The procedures indicated
should be carefully followed. Failure to do so can result in
improper installation which could cause bearing performance
problems as well as serious personal injury.
Bearings in bolt-on housings (units)
Check area - Clean and organize bearing installation area
1
and keep well lit. Be sure mounting surfaces are clean and
flat.
Check shaft - Shaft should be within tolerance range shown
2
in Table 20, clean, and free of nicks and burrs. Mount
bearing on unused section of shafting or repair/replace
shafting as required.
Table 20: Shaft Size Tolerances
Shaft Size (in)
1-11/16 to 2-7/16
2-7/16 and up
Install unit - Slide unit onto shaft. If it is difficult to mount
3
bearing on shaft, use a piece of emery cloth to reduce any
high spots on shaft. Do not hammer on any component of
the bearing.
Fasten unit in place - Install housing mounting bolts, check
4
and align bearing and tighten mounting bolts to
recommended fastener torques. Exercising extreme caution
and safety, rotate shaft slowly to center bearing.
NLGI
Base
Thickener
grade
Parafinic
Lithium
mineral oil
Mineral oil
Lithium
Synthetic
Lithium
Synthetic
Lithium
Mineral oil
Lithium
Shaft Size
Grams
20 mm
0.85
25-30 mm
2.84
35-40 mm
4.25
45-50 mm
5.67
55-60 mm
8.51
65-70 mm
15.59
75-80 mm
24.10
85-105 mm
42.53
Tolerance
+0 to -0.0015
+0 to -0.002
McQuay IM 937
2
2