Page 1
IM-5WMF (SEER13)-0706-McQuay Installation and Maintenance Manual Group: Wall Mounted Part Number: R08019028218 Date: July 2006 M5WM Wall Mounted Split Type Air Conditioner (SEER 13) Indoor Unit Wireless Remote Control (Standard) Wired Wall Control (Optional) Outdoor Unit...
Table of Contents General Information……………………………………………….. 3 Unit Indicator Lights ……………………………....19 Safety Precautions………………………………………. 3 IR Signal Receiver ………………...…………… 19 Unit Dimensions…………………………………………….……... 4 Cooling Only Unit ……………………....19 Indoor Units ……………………………………. ……..4 Heat Pump Unit ………………………....20 Outdoor Units …………………………….…….. ……..4 Special Features …………………………………..…..
General Information This manual provides installation procedures your conditioner unit operates properly and provides you the service CAUTION it was designed to provide. Special adjustment may be necessary to suit Use copper conductors only. Unit terminals are not local requirements. Before using your air designed to accept other types of conductors.
Installation Guidelines Installation Diagram Condensate Disposal of Outdoor Unit (Heat Pump Unit Only) • There are 2 holes on the base of outdoor unit Room Cabinet for condensed water to flow out. Insert the Indoor Unit drain elbow to one of the holes. •...
Piping Mounting Plate Installation The refrigerant piping can enter the indoor unit at several The mounting plate ships attached to the back of the different locations. Use the knock outs provided in the room indoor unit. To detach for mounting on wall, remove cabinet.
Drain Hose Installation Installing Unit on Mounting Plate The condensate drain hose (20” long) come factory Hook the indoor unit onto the upper portion of the mounting attached to the indoor unit. It is gravity flow. Avoid plate (engage the two hooks at the rear top of the indoor situations that could restrict drainage.
Figure 11. Cutting and Flaring Tube Refrigerant Tubing Tubing Length & Elevation Copper tubing to connect the indoor and outdoor units is supplied by others or it can be ordered from the factory. See Table 1 for requirements. Cover both tubes individually with 3/8”...
Electrical Connections Figure 14. Terminal Block and wire Clamp WARNING Improper installation can cause severe personal injury or death. Wiring must be done by a qualified electrician in compliance with local codes. Model 10F, 10FR, 15F and 15FR are using two separate power supply.
Figure 16. Cooling Only Size 20 & 25 Figure 17. Heat Pump Unit Size 20 & 25 Indoor Unit Outdoor Unit Terminal Block Connecting Wires Terminal Block COMP COMP Outdoor coil sensor, 2 conductor cable, (26 feet long) shipped with the indoor unit. Extend with 22 ga. low voltage wire if not long enough to reach outdoor unit.
Vacuuming and Charging Purging the Piping and the Indoor Unit Charge Operation Except for the outdoor unit which is pre-charged with This operation must be done by using a gas cylinder refrigerant, the indoor unit and the refrigerant connection and a precise weighing machine. The additional charge pipes must be air-purged because the air containing is topped-up into the outdoor unit using the suction moisture that remains in the refrigerant cycle may cause...
Special Precautions When Unit Indicator Lights IR Signal Receiver Dealing With R410A Unit When an infrared remote control operating signal is R410A is a new HFC refrigerant which does not damage transmitted, the signal receiver on the indoor unit beeps to the ozone layer.
Heat Pump Unit Table 7 shows the LED indicator lights for the heat pump unit under normal operation and fault conditions. The LED indicator lights are located at the bottom right side of the indoor unit. The heat pump units are equipped to maintain selected room temperature by switching automatically to either “cool” or “heat”...
Special Features Dry Mode Overheating Protection (Heat Pump Only) • Select this mode when the standard Cool mode does • If the indoor coil temperature exceeds 145ºF because not provide sufficient dehumidification. The compressor of high ambient conditions, dirty air filter, etc., the and indoor low fan will cycle together and will operate compressor will turn off.
Figure 25. Installing Filters Low Ambient Kit With this option, the unit can cool down to 32ºF outdoor temperature. (Standard units only cool down to 66ºF). To install, wire the Fan Speed Control Module (FSCM) in the outdoor unit per wiring diagram supplied with the kit. Attach the Outdoor Coil Sensor to the return bend as shown in Figure 26.
Remote Controller Operation Guide 1) Transmission Source • The source where the signal is transmitted. 2) Signal Transmission Indication • Blinks to confirm the last setting has been transmitted to the unit. 3) “ON/OFF” Button • Press once to start the unit. •...
Page 25
11) Sleep Mode Setting • Press the SLEEP button will activate the sleep mode function. • This is an energy saving option. When the unit is operating under cooling mode, the set temperature is increased by 0.5ºC after the first half an hour, another 0.5ºC after the second half an hour and 1ºC after the following 1 hour. This function will prevent excessive cooling during summer season.
Service and Maintenance Troubleshooting CAUTION If any malfunction of the unit is noted, immediately switch off the power supply. Check the following chart for possible causes/treatments. Disconnect electrical power supply before performing service, maintenance trouble persists, please call your local troubleshooting.
Page 27
This document contains the most current product information as of this printing. The manufacturer reserves the right to revise any of the specification and design contain herein at any time without prior notification.