McQuay SWP Series Installation And Maintenance Manual page 15

Self-contained air conditioning system, vintage sizes 018 through 105, microtech iii unit controller
Table of Contents

Advertisement

Table 8: Electric Heaters
208 V, 60 Hz, 3 phase
SWP unit size
kW
018 to 040
27.8
045 to 105
55.6
Table 9: SAF Motor Nameplate Amperage
Horsepower
3
Premium efficiency
5
Premium efficiency
7.5
Premium efficiency
10
Premium efficiency
15
Premium efficiency
20
Premium efficiency
25
Premium efficiency
30
Premium efficiency
40
Premium efficiency
50
Premium efficiency
60
Premium efficiency
a. 460/60/3 motors are used. Derate nameplate horsepower to 0.83 to obtain actual horsepower.
McQuay IM 937
230 V, 60 Hz, 3 phase
MBh
FLA
kW
MBh
94
77.2
34
116
190
154.4
68
232
Type
High efficiency
High efficiency
High efficiency
High efficiency
High efficiency
High efficiency
High efficiency
High efficiency
High efficiency
High efficiency
High efficiency
400 V, 50 Hz, 3 phase
FLA
kW
MBh
FLA
85.6
25.7
88
37.2
170.9
51.4
175
74.4
208/60/3
230/60/3
FLA
FLA
9.9
9.0
9.3
8.2
16.1
14.0
15.7
13.6
25.0
21.6
22.3
20.0
33.0
28.0
29.0
25.8
44.8
40.6
43.4
37.8
61.0
50.0
57.0
49.0
74.0
62.0
70.0
61.0
86.5
75.0
83.3
72.4
117.0
102.0
110.0
96.0
140.0
124.0
137.0
120.0
154.0
144.0
160.0
140.0
Electrical Data
460 V, 60 Hz, 3 ph
575 V, 60 Hz, 3 phase
kW
MBh
FLA
kW
34
116
42.8
34
68
232
85.6
68
a
400/50/3
460/60/3
FLA
FLA
4.5
4.5
4.1
4.1
7.0
7.0
6.8
6.8
10.8
10.8
10.0
10.0
14.0
14.0
12.9
12.9
20.3
20.3
18.9
18.9
25.0
25.0
24.5
24.5
31.0
31.0
30.5
30.5
37.5
37.5
36.2
36.2
51.0
51.0
48.0
48.0
62.0
62.0
60.0
60.0
72.0
72.0
70.0
70.0
MBh
FLA
116
34.2
232
68.4
575/60/3
FLA
3.4
3.1
5.3
5.2
8.2
7.4
11.0
10.3
16.2
14.1
20.0
18.9
24.3
24.2
30.0
29.8
40.0
38.0
49.2
47.5
57.4
56.0
15

Hide quick links: