Test Running; Precautions On Refrigerant Leakage - Vivax HPS-22CH65AERI/O1 R32 User Manual

Table of Contents

Advertisement

Available languages

Available languages

VIVAX
TEST RUNNING 
 
 
Operate according to "key points for test running" on the electric control box cover.
 
 
 
 
 
 
 
 
Test running can not start until the outdoor unit has been connected to the power 
 
 
for 12 hours. 
 
 
Test running can not start until all the valves are affirmed open. 
 
 
 
 
 
 
 
 
 
 
PRECAUTIONS ON REFRIGERANT LEAKAGE 
 
 
When the refrigerant charge in appliance is more than 1.842kg, following requirments 
should be complied with. 
 
Requirments for charge limits in unventilated areas: 
The maximum refrigerant charge in appliance shall be in accordance with the following: 
or the required minium floor area Amin to install an appliance with refrigerant charge 
mc shall be in accordance with following: 
where 
m
 
is the allowable maximumm charge in a room, in kg  
max
is the room area, in m
A
 
is the required minimum room area ,in m
min
m
 
is the refrigerant charge in appliance, in kg 
c
LFL 
is  the  lower  flammable  limit  in  kg/m
refrigerant 
Install  mechanical  ventilator  to  reduce  the  refrigerant  thickness, under critical 
level. (ventilate regularly). 
Install  leak  alarm  facility  related  to  mechanical  ventilator  if  you  can  not  regularly 
ventilate.
 
 
 CAUTION 
5/4
m
 = 2.5 x (LFL)
max
A
= ( m
 / ( 2.5 x (LFL)
min 
c
 
30 
1/2 
 x 1.8 x (A)
5/4
 x 1.8))
2
 
  ,the  value  is  0.306  for  R32 
3
ENG 
 

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

Table of Contents