Checks to the refrigeration equipment 
 
Where electrical components are being changed, they shall be fit for the purpose 
and to the correct specification. At all times the manufacturer s maintenance and 
service guidelines shall be followed. If in doubt consult the manufacturer s technical 
department  for  assistance.  The  following  checks  shall  be  applied  to  installations 
using flammable refrigerants: 
 
The  charge  size  is  in  accordance  with  the  room  size  within  which  the  refrigerant 
containing parts are installed; The ventilation machinery and outlets are operating 
adequately and are not obstructed; 
 
If  an  indirect  refrigerating  circuit  is  being  used,  the  secondary  circuits  shall  be 
checked for the presence of refrigerant; marking to the equipment continues to be 
visible and legible. 
 
Marking and signs that are illegible shall be corrected; 
 
Refrigeration pipe or components are installed in a position where they are unlikely 
to  be  exposed  to  any  substance  which  may  corrode  refrigerant  containing 
components,  unless  the  components  are  constructed  of  materials  which  are 
inherently  resistant  to  being  corroded  or  are  suitably  protected  against  being  so 
corroded. 
9)
Checks to electrical devices 
 
Repair and maintenance to electrical components shall include initial safety checks 
and  component  inspection  procedures.  If  a  fault  exists  that  could  compromise 
safety,  then  no  electrical  supply  shall  be  connected  to  the  circuit  until  it  is 
satisfactorily  dealt  with.  If  the  fault  cannot  be  corrected  immediately  but  it  is 
necessary to continue operation, and adequate temporary solution shall be used. 
This shall be reported to the owner of the equipment so all parties are advised. 
 
Initial safety checks shall include: 
 
That  capacitors  are  discharged:  this  shall  be  done  in  a  safe  manner  to  avoid 
possibility of sparking; 
 
That  there  no  live  electrical  components  and  wiring  are  exposed  while  charging, 
recovering or purging the system; That there is continuity of earth bonding. 
10)
Repairs to sealed components 
a)
During repairs to sealed components, all electrical supplies shall be disconnected 
from the equipment being worked upon prior to any removal of sealed covers, 
etc. If it is absolutely necessary to have an electrical supply to equipment during 
servicing, then a permanently operating form of leak detection shall be located 
at the most critical point to warn of a potentially hazardous situation. 
b)
articular attention shall be paid to the following to ensure that by working on 
electrical components, the casing is not altered in such a way that the level of 
protection is affected. This shall include damage to cables, excessive number of 
connections,  terminals  not  made  to  original  specification,  damage  to  seals, 
incorrect fitting of glands, etc. 