TEST RUNNING 
Operate according to "key points for test running" on the electric control box cover.
Test running can not start until the outdoor unit has been connected to the power 
for 12 hours.
Test running can not start until all the valves are affirmed open. 
 
PRECAUTIONS ON REFRIGERANT LEAKAGE 
When the refrigerant charge in appliance is more than 1.842kg, following requirments 
should be complied with. 
Requirments for charge limits in unventilated areas: 
The maximum refrigerant charge in appliance shall be in accordance with the following: 
or the required minium floor area Amin to install an appliance with refrigerant charge 
mc shall be in accordance with following: 
where 
m
 
is the allowable maximumm charge in a room, in kg  
max
is the room area, in m
A
 
is the required minimum room area ,in m
min
m
 
is the refrigerant charge in appliance, in kg 
c
LFL 
is  the  lower  flammable  limit  in  kg/m
refrigerant 
Install  mechanical  ventilator  to  reduce  the  refrigerant  thickness, under critical
level. (ventilate regularly).
Install  leak  alarm  facility  related  to  mechanical  ventilator  if  you  can  not  regularly
ventilate.
 CAUTION 
5/4
m
 = 2.5 x (LFL)
max
A
= ( m
 / ( 2.5 x (LFL)
min 
c
2
30 
1/2 
 x 1.8 x (A)
5/4
2
 x 1.8))
2
 
  ,the  value  is  0.306  for  R32 
3
ENG 