Error codes
When a safety device is activated, an error code will be displayed on the user interface.
A list of all errors and corrective actions can be found in the table below.
Reset the safety by turning the unit OFF and back ON.
In case this procedure for resetting the safety is not successful, contact your local dealer.
ERROR CODE
The condenser outlet
refrigerant temperature
sensor (T3)error.
The ambient
temperature sensor (T4)
error.
Suction temperature
sensor(Th) error
Discharge temperature
sensor(Tp) error
Communication error
between main control
board PCB B and main
control board of
hydraulic module
MALFUNCTION OR
PROTECTION
FAILURE CAUSE
AND CORRECTIVE ACTION
1. The T3 sensor connector is loosen. Reconnect
it.
2. The T3 sensor connector is wet or there is
water in. remove the water, make the
connector dry. Add waterproof
3. The T3 sensor failure, change a new
1. The T4 sensor connector is loosen. Reconnect
it.
2. The T4 sensor connector is wet or there is
water in. remove the water, make the
connector dry. Add waterproof
3. The T4 sensor failure, change a new
1. The Th sensor connector is loosen. Re connect
it.
2. The Th sensor connector is wet or there is
water in. remove the water, make the
connector dry. Add waterproof
3. The Th sensor failure, change a new
1. The Tp sensor connector is loosen. Re connect
it.
2. The Tp sensor connector is wet or there is
water in. remove the water, make the
connector dry. Add waterproof
3. The Tp sensor failure, change a new
1. wire doesn't connect between main control
board PCB B and main control board of
hydraulic module. connect the
2. Communication wire sequence is not right.
Reconnect the wire in the right sequence.
3. Whether there is a high magnetic field or high
power interfere, such as lifts, large power
transformers, etc.. To add a barrier to protect
the unit or to move the unit to the other
37
-
VIVAX
adhesive
sensor.
adhesive
sensor.
adhesive
sensor.
adhesive
sensor.
wire.
place.