DO Channel
DO On Time(sec)
DO Off Condition
(2)
DO
Item
Cycle Time(sec)
Cycle Percent(%)
Auto-Stop Time(sec)
GT-540P-3GWA-OEM1 user's manual, Version 1.0, 2013/03
GT-540P-3GWA-OEM1 user's manual v1.0
Hold Time". The unit is second.
(Range : 0 ~ 65535 sec)
The text will define which DO channel will
output according to the DI triggering.
(Channel 0 ~ 1)
The DO channel would keep outputting
according to this time, when DI channel is
triggered and "DO Off Condition" is "time".
The unit is second.
(Range : 0 ~ 65535 sec)
These conditions of the DO terminating
outputting when DO is output by DI trigger.
1. Disable: Disable the DO linkage with DI
channel.
2. Time: The DO output would keeping "ON"
according to the "DO on Time" when DI is
triggered.
3. Input Status: The DO channel output would
be kept contiguously according to the time
of the "Return Hold Time" when the DI
returns to the non-trigger status
Description
The time of a duty cycle for DO.
If it is 0, duty cycle function is disabled.
(Range : 0 ~ 65535 , Unit : Second)
The percentage of DO output would keeping
"ON" in a duty cycle.
(Range : 0 ~ 100, Unit : %)
If the GT-540P-3GWA-OEM1 disconnect to
RTU Center over this time, the operation of
duty cycle would be stopped automatically.
If it is 0, the GT-540P-3GWA-OEM1 does
not stop the operation of duty cycle
automatically.
(Range : 0 ~ 65535 , Unit : Second)