Analog Outputs
Two analog outputs are provided, both can be configured for a signal level of 0 to 10 VDC or 4 to 20 mA. The signal
level is controlled by the position of jumpers J2 and J3 on Control PCB A2 and by the values selected for Drive
parameters H4-07 and H4-08.

Configuring the Analog Outputs:

Terminals
Analog
AC
Output
Common
TB3-4
TB3-1
TB3-4
TB3-1
TB5-6
TB5-7
TB5-6
TB5-7
* = For Drive programming reference

Programming the Analog Outputs:

The TB3-4 and TB5-6 analog outputs can be programmed to be proportional to any of the following Drive variables.
Setting
1
2
3
6
7
8
15
16
18
* SFS is the internal soft starter signal. This signal is generated from the reference and often it passes through the accel/ decel functions.
See the H4-0X parameters in programming manual TM.E7.02 for additional programming details.
Table 1.6 Analog Outputs
Jumper Position
Signal Level
J2
4-20 mA
1-2
0-10 VDC
2-3
4-20 mA
N/A
0-10 VDC
N/A
Table 1.7 Analog Output Proportional Variables
Description
Frequency Ref
Output Freq
Output Current
Output Voltage
DC Bus Voltage
Output kWatts
Term A1 Level
Term A2 Level
Mot SEC Current
Parameter
J3
Terminal *
N/A
FM
2: 4-20 mA
N/A
FM
0: 0-10 V
1-2
AM
2-3
AM
Setting
Description
20
SFS Output*
24
PI Feedback
31
36
37
38
PI Setpoint
51
Auto Mode Fref
52
Hand Mode Fref
53
PI Feedback 2
Yaskawa Electric America, Inc.
Installation Guide IG.E7B.02 Rev: 04-11
Drive
Parameter
H4-07
H4-08
N/A
N/A
N/A
2: 4-20 mA
N/A
0: 0-10 V
Not Used
PI Input
PI Output
Date: 11-1-04 Page 7 of 46