8.D.10.g Trim
To navigate to the Trim Menu, touch the Trim Icon on the Miscellaneous Menu Screen.
This O 2 Trim Menu allows you to
• Enable/Disable
NOTE: All Service Options for
O 2 Trim are available only with
the OEM Login.
8.D.10.h Isolation Valve
To navigate to the Isolation Valve Menu, touch the Isolation Valve Icon on the Miscellaneous Menu Screen.
The Isolation Valve Configuration Screen allows adjustment of the following parameters:
Enable/Disable – Enables/disables the isolation valve functionality.
Open Time Delay – The amount of time the controller expects to receive indication that the isolation valve is open.
Close Time Delay – The amount of time the controller expects to received indication that the isolation valve is closed.
Manual Operation – Allows the user to select manual or automatic isolation valve operations.
Manual Open/Close – If manual
operation is selected, this will
manually open/close the isolation
valve.
Min. Number of Open Valves – This
parameter allows the user to select
the number of isolation valves that
must remain open to satisfy system
flow requirements.
C O N F I G U R A T I O N
FT
(O 2 Trim Enable / Disable)
Page 95