Bradford White Laars Linc MagnaTherm FT CFH1000 Installation And Operation Instructions Manual page 111

Table of Contents

Advertisement

Model
All Models
Table 22. Combustion Settings.
8. If needed, adjust the fuel pressure adjustment
screw (See Figure 51) to obtain a
CO 2 measurement of 9.0% +/- 0.2%.
NOTE: Turn the adjustment screw only a
quarter turn per adjustment either up or down,
then watch the combustion analyzer for the
result.
Once the Hi-Fire CO 2 is within the range
shown above, move on to Step 9.
If the gas pressure is within range and the Hi-
Fire CO 2 will still not adjust to an acceptable
level,
then Call Factory.
9. With the High-Fire CO 2 stabilized and
acceptable at 9.0% +/- 0.2%, go to the
touchscreen display and adjust the Manual
Firing Rate to 5% for Low Fire combustion.
10. Wait until the combustion analyzer stabilizes
at the 5% rate (at least 5 minutes), to observe
the new CO 2 and CO readings.
CO 2 at Low-Fire is 'Greater than 8.0%
& less than 9.2%'. DO NOT ADJUST
AT LOW-FIRE.
If Low-Fire is NOT within range, then go back
to Step 5 and Repeat, adjusting only at High-
Fire.
Additionally, CO needs to be less than 50
PPM.
Check again that the incoming gas supply
pressure falls within the correct range.
See Table 23 on page 111
11. If a High-Fire CO 2 of 9.0% +/- 0.2% and at
Low Fire CO 2 of greater than 8.0% & less
than 9.2% can NOT be achieved, then call the
Manufacturer.
If these parameters have been achieved, then
12. Disable Manual Firing Rate
13. Return to the O 2 Configuration Menu and
Enable the O 2 Trim.
FT
Gas Type
High-Fire CO 2
9.0% +/- 0.2%
Natural
Hi-Fire
Acceptable
Maximum CO (ppm)
Low-Fire CO 2
Greater than 8.0%
& less than 9.2%
Natural Gas
4.0 IN - W.C.
Min
10.5 IN - W.C.
Max
Table 23. Gas Pressure
Page 111
50
LP (propane)
8.0 IN - W.C.
13.0 IN - W.C.

Advertisement

Table of Contents
loading

Table of Contents