Download Print this page

EBARA DSC4 Series Operating Instructions, Installation & Maintenance Manual page 5

Submersible wastewater, sewage pump

Advertisement

INSTRUCTION MANUAL
Support the guide pipe with bushings on discharge elbow and the guide pipe holder.
If the guide pipe requires a length exceeding 5.5m (18ft), an extension or
intermediate support may become necessary, in which case we are available for
consultation. When installing the discharge elbow, the guide pipe must be vertical
(with a tolerance of 1mm (0.04in) or less per 1m (3.3ft)), using a plum bob. If it is not
vertical, it may become impossible to lift pump. Discharge elbow level should be
within 0.1mm (0.04in) per 1m (3.3ft), both in the "X" and "Y" directions shown in Fig.
4. It is recommended practice that pipe installation be carried out with the discharge
elbow covered to protect against entry of concrete and mortar during the work.
CAUTION : FIX THE ANCHOR BOLTS TIGHTLY BY, FOR EXAMPLE, BY
!
WELDING THEM TO THE REINFORCEMENT BAR, ETC.
3.4 Discharge Pipe Installation (Fig. 5)
When mortar under discharge elbow has been sufficiently set, proceed with piping to
the discharge side.
CAUTION : DURING THIS WORK, TAKE CARE NOT TO SUBJECT THE
!
DISCHARGE ELBOW TO EXCESSIVE WEIGHTS.
PM32U
Fig 4
P.4