This is done via the natural draught system. All Element4 gas fires are tested for flue gas discharge through the wall (C11), through the roof (C31) or with flexible exhaust pipes through an existing chimney (C91) The diameter of the duct can be 150/100 mm or 200/130 mm, depending on the fireplace and the course of the flue gas duct.
• If the flue run is only running vertically with no bends then you can use a reducer so you can use 150/100mm or 6/4 inch flue on most Element4 fires – but not all For Element 4 fireplaces, to not reduce the flue diameter is preferable for optimal operation of the fireplace.
Page 5
Flue calculation manual You do not have to include the first 3 N-bends (from vertical to horizontal) in your calculations. The next bends of type N are each counted as 1 horizontal meter in the THL. For a bend of type Q (horizontal to horizontal): •...
Flue calculation manual Flue calculation example The six questions of flue calculation To find out whether the desired flue configuration is possible for your fireplace, the following six questions can be asked: 1. In what category is the fire that is to be installed. Use the table in chapter 3 as a guideline .
Flue calculation manual Example flue configuration Horizontal or vertical terminal Bend 45° & 90° vertical to horizontal and vice versa Bend 45° & 90° horizontal to horizontal Pipe section horizontal Pipe section vertical...
Flue calculation manual Category 1 (Metric) – Ratio 1:4 The tables below are the same for fireplaces with spigot diameter 200/130 and 150/100. Fires in this category are never to be reduced to ensure a correctly functioning fireplace. 3.1.1 Calculation table horizontal terminal (C11) Total Horizontal Length 3.1.2 Calculation table vertical terminal (C31)
Page 10
Flue calculation manual For a vertical terminal a Total Vertical Length of at least 2 meter is necessary! Total Horizontal Length...
Flue calculation manual Category 2 (Metric) - Ratio 1:2.5 The tables below are the same for fireplaces with spigot diameter 200/130 and 150/100. Fires in this category are never to be reduced to ensure a correctly functioning fireplace. 3.2.1 Calculation table horizontal terminal (C11) 2.5 3.5 Total Horizontal Length 3.2.2...
Flue calculation manual Category 3 (Metric) – Ratio 1:2 3.3.1 Calculation table horizontal terminal (C11) pipe diameter 200/130 Total Horizontal Length 3.3.2 Calculation table vertical terminal (C31) pipe diameter 200/130 Total Vertical Length For a vertical terminal a minimal starting length of 0,5m and minimal of 1 m is required.
Flue calculation manual Category 4 (Metric) – Ratio 1:1 3.4.1 Calculation table horizontal terminal (C11) pipe diameter 200/130 Total Horizontal Length 3.4.2 Calculation table vertical terminal (C31) pipe diameter 200/130 Total Vertical Length For a vertical terminal a minimal starting length of 0,5m and minimal of 1 m is required.
Flue calculation manual Category 5 (Metric) – Ratio 2:1 Fires in this category are never to be reduced to flue diameter 150/100mm. For the Modore /Tenore 240 a restriction plate is never necessary. 3.5.1 Calculation table horizontal terminal (C11) pipe diameter 200/130 Total Horizontal Length 3.5.2 Calculation table vertical terminal (C31) pipe diameter 200/130...
Flue calculation manual Category 1 (Imperial) – Ratio 1:4 The tables below are the same for fireplaces with spigot diameter 8/5 and 6/4. Fires in this category are never to be reduced to ensure a correctly functioning fireplace. 3.6.1 Calculation table horizontal terminal (C11) 13'6"...
Flue calculation manual 3.6.3 Calculation table pipe diameter 6/4 Please note: This table is only applicable when flue is reduced. Fireplaces with a 6/4 spigot do not apply to this table, but instead table 3.1.1 3.1.2 is to be used. Total Vertical Length For a vertical terminal a of at least 7 feet is necessary!
Flue calculation manual Category 2 (Imperial) - Ratio 1:2.5 The tables below are the same for fireplaces with spigot diameter 8/5 and 6/4. Fires in this category are never to be reduced to ensure a correctly functioning fireplace. 3.7.1 Calculation table horizontal terminal 13'6"...
Flue calculation manual Category 5 (Imperial) – Ratio 2:1 Fires in this category are never to be reduced to flue diameter 6“/4“. For the Modore /Tenore 240 a restriction plate is never necessary. 3.10.1 Calculation table horizontal terminal pipe diameter 8/5 13'6"...
Flue calculation manual Existing Chimney All Element4 gas fire places are CE approved with a C91 mark. This means that the fire can be installed with a flexible pipe in an pre-existing chimney, where the chimney is functioning as the air supply in a concentric flue system. The flexible pipe is the exhaust for the flue gasses.