12.3 3 SetFunction

SETUP
Service
1

12.3.1 Set the analogue output

Qmin:
Input of the fl ow rate, for which 4 mA should be output.
Qmax:
Input of the fl ow rate, for which 20 mA should be output.
12.3.2 Setting output functions and
switch points
K1 Switch:
Defi nes the output contact type.
NO – make contact or NC – break contact
K1 Fn:
Determines the function of output K1.
OFF
No function
Lower than the system flow rate specified
(Q min)
under AlarmMinK1
Exceeds the flow rate that is specified under
(Q max)
AlarmMaxK1
(Q min/max)
Lower or higher than the preset flow rate
Lower than the temperature value specified
(T min)
under AlarmMinK1 (only for device version
MT2)
Exceeds the temperature value specified
(T max)
under AlarmMaxK1 (only for device version
MT2)
Lower or higher than the specified
(T min/max)
temperature value (only for device version
MT2)
Lower than the total flow rate value that is
(TQ1 min)
preset under AlarmMinK1
Exceeds the total flow rate value that is
(TQ1 max)
preset under AlarmMinK1
Lower or higher than the preset total flow
(TQ1 min/max)
rate value
Lower than the total flow rate value that is
(TQ2min)
preset under AlarmMinK1
Exceeds the total flow rate value that is
(TQ2 max)
preset under AlarmMinK1
Lower or higher than the preset total flow
(TQ2 min/max)
rate value
Direction
Change the flow direction
Warning
Warning message
AlarmMinK1:
Sets the lower trigger threshold under which output K1 is
switched.
AlarmMaxK1:
Sets the upper trigger threshold over which output K1 is
switched.
K1 delay:
Determines the delay time of relay K1.
3030 mFlow
SetBasics
SetFunction
2
3
SetCalibration
Communication
4
5
K2 Switch:
Defi nes the output contact type.
NO – make contact or NC – break contact
K2 F:
Determines the function of output K2.
OFF
No function
Lower than the system flow rate specified
(Q min)
under AlarmMinK2
Exceeds the flow rate that is specified under
(Q max)
AlarmMaxK2
(Q min/max)
Lower or higher than the preset flow rate
Lower than the temperature value specified
(T min)
under AlarmMinK2 (only for device version
MT2)
Exceeds the temperature value specified
(T max)
under AlarmMaxK2 (only for device version
MT2)
Lower or higher than the specified
(T min/max)
temperature value (only for device version
MT2)
Lower than the total flow rate value that is
(TQ1 min)
preset under AlarmMinK2
Exceeds the total flow rate value that is
(TQ1 max)
preset under AlarmMinK2
(TQ1 min/max) Lower or higher than the preset total flow
rate value
Lower than the total flow rate value that is
(TQ2min)
preset under AlarmMinK2
Exceeds the total flow rate value that is
(TQ2 max)
preset under AlarmMinK2
Lower or higher than the preset total flow
(TQ2 min/max)
rate value
Direction
Change the flow direction
Warning
Warning message
AlarmMinK2:
Sets the lower trigger threshold under which output K2 is
switched.
AlarmMaxK2:
Sets the upper trigger threshold over which output K2 is
switched.
K2 delay:
Determines the delay time of relay K2.
22 / 40