11 Parameter table

Configuration level
Display
Submenu for displaying inputs and outputs
1 Service
v
Q
T
Min - T - Max
Reset Min T Max
DIR
Output K1:K2:K3
I out
TQ1 mode
TQ1
TQ2 mode
TQ2
Submenu for setting access authorisations
Code
Logout
New Code: 1
New Code: 2
New Code: 3
Submenu for displaying diagnostic messages
Error List
hrs
Warnings
Clear Error List
Submenu for displaying the tool identification
Version
S/N
Configuration level
Display
Default
2 SetBasics
Display mode
Unit
Decimal point
Range
Low flow
Filter
F.Line
D.Refresh
DLight
AutoReturn
HelpLanguage
HelpText
Function
Current flow velocity
Current flow rate
Current temperature
Minimum and maximum temperature
value
Reset the temperature values
Shows the current flow direction
Status of the outputs K1, K2, K3
Value of current output in mA
Activate totalizer 1
Display the total flow rate of totalizer 1
Activate totalizer 2
Display the total flow rate totalizer 2
Password entry
Block access
Release the lowest priority
Release the medium priority
Release the top priority
Displays error messages
Displays operating hours
Display warnings during operation
Delete error list
Device version
Serial number
Function
Reset to factory settings
Selection of display indication
under normal working condi-
tions
Unit of measure of the flow
rate
Determines the number of
digits displayed after the
decimal point
Selection of measuring range
Leak flow volume suppression 0-10 %
Signal filtering
Input of mains frequency
Time for display refresh
Setting the display lighting
Time for an automatic return to
the working level
Text language
Display the help text
15 / 40
Value range
± 12.00 m/s
± 90,000,000 l/h
0 to 100 °C
0 to 100 °C
Positive/negative
0 to 22.0 mA
OFF/ON
90,000,000,000 l
OFF/ON
90,000,000,000 l
0...10000
OK
0...10000
0...10000
0...10000
0 to 9999 h
ON / OFF
OK
Value range
Yes / No
Q+v
Q+TQ1
Q+TQ2
v+TQ1
v+TQ2
TQ1+TQ2
Q+T (only for version MT2)
v+T (only for version MT2)
,x / ,xx / ,xxx / Auto
Auto
0-4 m/s
0-10 m/s
0.1 to 99.9 s
50 Hz/60 Hz
0.1...1.0 s
OnKey / On
1 to 60 min
D / GB
ON / OFF
Factory setting
OFF
OFF
0
0
0
0
ON
Factory setting
Yes
Q+v
Auto
Auto
1 %
0.1 s
50 Hz
0.1 s
OnKey
5 min
D
ON