Chapter 5
Configure FLEX I/O Digital Modules on a DeviceNet Network
Determine the Address of
DeviceNet Data
input data from the scanner
output data for the scanner
status data from the scanner
The scanner memory uses this format:
slot
type
.Data
Where:
Is:
slot
slot number of the scanner
location
If you have this scanner:
local ControlLogix 1756-DNB
remote ControlLogix 1756-DNB
CompactLogix™ 1769-SDN
SoftLogix™ 5800 1784-PCIDS
DriveLogix™/FlexLogix™ 1788-DNBO
Linking Device 1788-EN2DN or
1788-CN2DN
type
If the data is:
input from a device
output to a device
status of the network
element
specific DINT (DWord, 32-bit integer) within the array
bit
specific bit within an integer
54
When you add the scanner to the I/O configuration of the controller,
RSLogix 5000 software automatically creates a set of tags for the input, output,
and status data of the network:
The tags for your DeviceNet data follow this format:
[element]
.bit
Then location is:
Local:slot_number_of_scanner
name_of_remote_bridge:slot_number_of_scanner
Local:slot_number_of_scanner
Local:slot_number_of_scanner
name of the scanner in the I/O configuration of the controller
name of the linking device in the I/O configuration of the controller
Then type is:
I
O
S
Which is this tag in the controller
location
:type
.Data
Rockwell Automation Publication 1794-UM061B-EN-P - March 2020
[element]
.bit
= Optional