Making J210 Connections; Wiring - Xantrex XPD 120-4.5 Operating Manual

Xpd 500 watt series programmable dc power supply
Table of Contents

Advertisement

Making J210
Connections

Wiring

For most connectors and jumpers, use any suitable wire such as 16 to 24 AWG
stranded wire. For lowest noise performance, use shielded pair wiring of 16 to 24
AWG. Use the shortest leads possible. Ground the shield to pin 8 (auxiliary ground)
on the J210 connector or to the chassis via one of the J210 connector screws.
Release A
CAUTION
!
Program/monitor signal and return are internally connected to the power
supply negative output. Do not attempt to bias these away from that
potential.
CAUTION
!
To maintain the isolation of the power supply output and prevent ground
loops, use an isolated (ungrounded) programming source when operating
the power supply via remote analog control at the J210 connector.
CAUTION
!
Before making connections from external circuits to the J210 connector, turn
the power supply OFF and wait until the front panel displays have gone out.
WARNING
There is a potential shock hazard at the output when using a power supply
with a rated output greater than 40 V. Use load wiring with a minimum
insulation rating equivalent to the maximum output voltage of the power
supply. For example, select TEW, 105
120 V, 4.5 A power supply.
Section 1. Features and Specifications
Rear Panel Connectors
°C, 300 V wiring for use with a
17