3-Phase, 3-Wire Delta Output Wiring; 3-Phase, 3-Wire Y-Connection Output Wiring - Xantrex XDI2048 Operating Manual

2kva/1.5kw datacom inverter
Table of Contents

Advertisement

Rack Mount Frame Assembly and Installation

3-Phase, 3-Wire Delta Output Wiring

3-Phase, 3-Wire Y-Connection Output Wiring

2-20
All outputs should be wired through an appropriately rated circuit
breaker.
On Phase-1, Connect terminal L1 to phase-3 Terminal L2.
On phase-1, connect terminal L2 to phase-2 terminal L1.
On phase-2, connect terminal L2 to phase-3 terminal L1.
All outputs should be wired through an appropriately rated circuit
breaker.
Connect L2 terminals of the three phases to a common bus.
Wire L1 of phase-1 to Line-1 output.
Wire L1 of phase-2 to Line-2 output.
Wire L1 of phase-3 to Line-3 output.
L1
L2
L1
L2
L1
L2
L1
L2
L1
L2
L1
L2